Mount the runners on the burner hatch flange. Secure the guide lugs onto the mounting bracket
with screws, and the mounting bracket at the bottom edge of the burner, angled back out from
the boiler. First apply the sealing braid as shown in the picture, then push the burner back into
place. It may be necessary to lift the burner a little from runner sled. Screw the burner securely
to the burner hatch flange using the 4 nuts enclosed. If necessary, adjust the height of the run-
ners afterwards. Connect the cables on the side of the burner.
INSTALLATION OF THE BURNER
1. Installation of the immersion heater
2. Installation of the thermostat
Electrical operation:
An immersion heater (6 or 9 kW) can be installed in the boiler, in the DN 50 connection, on
the side closest to the front of the boiler (14). The immersion heater is delivered together with
an adjustment/overheat thermostat TY3. Detailed instructions for connection are enclosed
with the thermostat.
Fuse sizes: 6 kW immersion heater 3x10 A and 9 kW immersion heater 3x16 A.
Supply voltage: 400 V, 3~, 50 Hz
NOTE! A safety switch must be installed in the immersion heater's power supply.