MENU STRUCTURE
The following tables give an overview of the messages that may appear on the display of the
control unit. They also indicate which parameters the user is allowed to change freely and
which parameters he/she is allowed to change only if instructed to do so by an authorised in-
staller. NOTE! Part of the menu options are displayed only when they are active.
Menu
Setting
Description
Temperature
Boiler xx (80) °C
5-95°C
Boiler temperature, set temperature in brackets.
Fluegas xx (250) °C
120-280°C
Flue gas temperature, alarm limit in brackets.
Residual oxygen x.x%
-
Displays the amount of residual oxygen while
the burner is in Maintain mode (Accessory)
Burner Off (On) mode
On/Off
Burner start-up and stop. Burner operating mode
below. Example: Output MAX
Auger external
manual Off (On)
On/Off
External auger start-up (visible if the burner is
in Off mode). The remaining operating time is
shown in brackets. Can be stopped manually.
Fuel
Pellets
P electricity
Electricity
Heating method selection (visible if the electrical
resistances are being used and the burner is in
On mode - see "Burner Settings").
Outdoor xx°C / Heat xx(xx) °C /
Room xx(xx) °C
Room 0-30°C
Temperature display of heat regulation circuits
(visible if activated from the Accessories menu).
Adjust
0-20 °C
Fine adjustment of heating circuit 1 (visible if
activated from the Accessories menu and if the
internal sensor is not connected)
Menues
-
Accessing submenus: Burner Adjustments, Ope-
rating Time, Pellet Store, Power, Heat Regulati-
on, Service.
Main menu
Menu
Setting
Description
El step
0-3
Activation of electrical resistances
0 = not in use,
1= 3 kW
2=6 kW
3= 9 kW
Start backup El
10-40 °C
Activation temperature of electrical resistances.
Level monitor 99% (50%)
10-90%
Displays the pellet level between the level swit-
ches of the burner. The auger starts when the
value falls below 50 %.
Optical monitor 99%
(50%)
1-98%
Displays the flame strength.
Limit value in brackets.
Test outputs
-
The burner functions (e.g., auger burner, blower,
etc.) can be tested in the menu.
English
Suomi, Svenska, English, Ger-
man, Italiano, France, Spain,
Russia
Menu language selection
Factory settings v110311
Yes / No
Restores the original factory settings.
Diff temperature No
No, 5-60°C
Burner operating lag time. The burner moves to
Maintain mode at the target temperature and
restarts when the temperature has decreased by
an amount equal to the lag time.
No = hysteresis 5 °C
5-60 °C = the burner runs only on Max. output.
Accessories
-
The menu can be used to take accessories into
use.
Adjustments menu
Text on the display
Setting
Description
Total xx h
-
Burner total operating time in Power mode.
High xx h
-
Burner operating time at Max power.
Low xx h
-
Burner operating time at Mean power.
Min xx h
-
Burner operating time at Min power.
El 1
-
Operating time of the 6 kW electrical resistance.
El 2
-
Operating time of the 3 kW electrical resistance
Operating Time menu