21
Malfunction
Cause
Action
The AVTA valve is leaking
water.
Impurities in the valve.
Remove and clean.
The pulse-controlled burn back
protector valve is leaking water.
Impurities in the valve or the flow
direction of the valve is wrong.
Remove and clean, check flow direc-
tion.
The pulse-controlled burn back
protector valve does not open.
Network pressure too high.
Reduce pressure to 3 bar.
Insufficient heat.
Storage auger feed insufficient,
smoke entering the intermediate
tank and disturbing the photocell.
Ensure sufficient underpressure in the
boiler.
Dust from the fuel disturbing the
photocell in the intermediate
tank.
Hopper filling time must be shortened
to 8-12 secs.
The unit has stopped. Alarm.
Check what is causing the alarm.
Find out the reason for the alarm..
TROUBLE-SHOOTING