background image

 PELLET STOKER KMP PX50

ARITERM SWEDEN AB

 

  

Installation Instructions - 

2007.12.14 - 11/16

Outer tube

Inner tube

Pellet stop

Rear housing

Igniter console

Ignitor element tube

Transformer 

Blower

Control panel

Connectors

Feeding tube

Cut-out thermostat

  Exploded view / Technical data

  Technical data

Dimensions outside boiler (b x h x d) ........ 300 x 310 x 300 mm
Dimensions inside boiler (Ø x l) ........................ Ø180 x 200 mm
Efficiency ..................................................................... ca 95%
Output maximum .......................................................... 50 kW
Output minimum .......................................................ca 20 kW
Voltage ...................................................................... 230 VAC
Power consumtion (mean under power) ...........................50 W
Weight ............................................................................12 kg
Length standard screw feeder ......................................... 1,7 m

  Accessories and fittings

• Adaptor plate
• Adaptor plate with flange
• Overheat cut-out thermostat for boiler
• Longer screw feeder
• Suspension chain for screw feeder
• Ash separator for vacuum cleaner

Summary of Contents for PX50

Page 1: ...DIRECTIONS FOR INSTALLATION AND USE PX50 ...

Page 2: ...for start and stop and a control screw to adjust the desired working temperature of the boiler Three control lamps indicate that 1 current is on green above On Off switch stoker is in full power mode green stoker is igniting green blink stoker is standing by green slow blink 2 stoker is in low power mode yellow 3 shut down red shut down in full power mode red green shut down in low power mode red ...

Page 3: ... connecting feeder and stoker see section Start och adjustment Important The flue valve if any must be kept fully open at all times All hatchets and flue pipes must be airtight This is particularly important if the chimney is tight or there is a low draught for any other reason Otherwise there is a risk of smoke going backwards during startup especially if the stoker is not properly adjusted Screw...

Page 4: ...wer parts of the chimney If so the flue gas temperature has to be rizen If there is only a small amount of moisture in the upper part installation of a draught pass might be sufficient Alternatively the stoker can be run only in full power mode If large amounts of moisture appears installation of a stainless steel insert tube is the best solution If the draught in the chimney burner reacently stop...

Page 5: ... be made with the enclosed cables and connectors NOTE The stoker has to be connected to the mains on a manual reset cut out thermostat on the boiler The bulb of the cut out thermostat has to be immersed in the boiler water or other wise located on the boiler where a quick action is guaranteed in case of overheating If there is no thermostat on the boiler an external one has to be installed optiona...

Page 6: ...about 3 4 of a turn every 20 th second Fine tuning full power In order to get optimal result a flue gas tester must be used Consult your local ditributor It is important to achieve the right mixture between fuel and air to get good economy A few minutes after startup the blaze should have a yellow white colour If it is dark yellow there is too much fuel or too less air A very light blaze indicates...

Page 7: ... and shunt valve is situated in in the tank the temperature sensor can alternatively be placed on the tank this leading to longer running intervals thus mini mizing the number of starts and stops Placing the temperature sensor on the tank If the temperature sensor is to placed on the storage tank the charging pump system must have capacity enough to cool the boiler off sufficiently Boiler temperat...

Page 8: ...st two months after installation The burner must be dismantled at least four times per year The outer and inner burner tubes should be separated and cleaned from sintered ashes Dismantle by loosing four screws on the front of the stoker Note that all cables have to be unplugged before removing the cover Safety systems The PX50 stoker meets all current safety regulations and standards There are two...

Page 9: ...cover and pull the cover backwards 3 Disconnect the white wires from the terminal block no 17 18 and pull the sensor out of its hole to the left of and beneath the ventilator 4 Push the new sensor into the hole until it gets stuck Be sure to align it perpendicular to the surface Reconnect the wires on the terminal block and refit the cover Dismantling the screw feeder 1 Disconnect the cable on the...

Page 10: ...ormally heating element will glow 1 minute after finished start dose If no glow first check all wires and connections then the glow coil 120 145 Ohms If alright change the ignition controller Fault Cause What to do Stoker doesn t ignite remaining pellets in stoker not scorched Faulty ignition element See section Changing the heating element Fault Cause What to do Stoker stops now and then without ...

Page 11: ...a Technical data Dimensions outside boiler b x h x d 300 x 310 x 300 mm Dimensions inside boiler Ø x l Ø180 x 200 mm Efficiency ca 95 Output maximum 50 kW Output minimum ca 20 kW Voltage 230 VAC Power consumtion mean under power 50 W Weight 12 kg Length standard screw feeder 1 7 m Accessories and fittings Adaptor plate Adaptor plate with flange Overheat cut out thermostat for boiler Longer screw f...

Page 12: ...PELLET STOKER KMP PX50 ARITERM SWEDEN AB Installation Instructions 2007 12 14 12 16 Warranty For warranty issues Ariterm Sweden AB refers to our local Distributor ...

Page 13: ... draught cold Pa Temperature outside C Flue gas temperature max power C CO2 content Chimney draught hot Pa Boiler make model Year manufactured Installed at Name Telephone Address Postal address Sold by Seller Company Address Postal address Telephone Mobile Installed by Assembler Company Address Postal adress Telephone Mobile Installed product Pellet stoker type PX50 ...

Page 14: ......

Page 15: ...draught cold Pa Temperature outside C Flue gas temperature max power C CO2 content Chimney draught hot Pa Boiler make model Year manufactured Installed at Name Telephone Address Postal address Sold by Seller Company Address Postal address Telephone Mobile Installed by Assembler Company Address Postal adress Telephone Mobile Installed product Pellet stoker type PX50 ...

Page 16: ...ation and maintenance the obligations of Ariterm Sweden AB under the warranty regulations are no longer binding Ariterm reserve the right to alter any details and specifications without prior notice Ariterm Sweden AB Flottiljvägen 15 SE 392 41 Kalmar www ariterm se ...

Reviews: