MAINTENANCE
Maintenance intervals
The following maintenance intervals are indicative and may vary considerably according to the
chosen fuel and the heat load. Note that keeping up a very small fire stains the boiler heavily.
At first the maintenance is to be performed more reqularly in order to determine the suitable
interval for the maintenance. If the fuel quality changes the maintenance interval must be
redetermined. During winter the heating requirement is greater than in the summer and
therefore the maintenance interval may be shortened compared to summer.
*) Using fuel that creates a lot of ash will naturally increase the amount of ash and thus shorten
the maintenance interval.
BioComp -series
Interval*)
Sweeping the convection part
Every 4-6 months. Spirals to be removed from
the convection part before the sweeping.
Sweeping the fire chamber
Once a year.
Ash removal from the fire chamber
Inspection: 1-2 times a month. If the system has
fire chamber ash screws the interval is longer.
Ash removal from under the convection part
Inspection: Once a month. If the system has
convection part ash screws the interval is longer.
Visual inspection of the boiler
Inspection: Once a month (pipe connections).
Checking the safety valves
Twice a year.
Checking the tightness of the sealings and
hatches (replace if necessary)
Inspection: Once a month.
Burner maintenance according to the burner
manual