background image

Filter Dryer (Biflow type)

Must be replaced if the system is opened.

Drip Tray Drains

All drains should be trapped externally to the unit.

Compressor Bracket

Do not remove compressor bracket, this bracket is for 

transport and for the operation of the compressor.

Electrical Connection

Tighten all electrical connections before starting and 

commissioning unit.

Phase Failure 

Relay

Fan Control Card. 

Adjust pots for speed  

control of supply & exhaust fans

Pipe Clamps

Tighten all pipe clamps before starting. These clamps 

may loosen in transport.

10               OAP – Outside Air Package Units Installation and Operation Manual 2021   

Summary of Contents for 0AP900

Page 1: ...Installation and Operation Manual OAP Outside Air Package Units 0AP900 OAP10000 M ADE A U STRALI A N Manufactured byArmcor M ADE A U STRALI A N Manufactured byArmcor...

Page 2: ...equirements Mains Power Supply and Fusing Standard Equipment Layout 8 Features 9 General Maintenance 11 General Monthly Maintenance Schedules Guide to How Frequency According to Usage is Established T...

Page 3: ...c Please contact our engineering team about your project to ensure the correct application of the OAP units The OAP unit can be provided with fixed speed compressors digital scroll or inverter compre...

Page 4: ...vice heat recovery and or air handling equipment Installing and servicing equipment can be hazardous due to electrical and mechanical components When working on equipment observe precautions in all li...

Page 5: ...d to the supply and return ducts to reduce any vibration transfer Fresh Air Inlet The location of the fresh air inlets must adhere to the Australian Standards AS 1668 2 The fresh air intake should be...

Page 6: ...y codes and guidelines Wear safety goggles work gloves work boots and protective clothing All external units are provided with substantial lifting lugs on each corner at the base frame NOTE All units...

Page 7: ...n commissioning Where a Heat Exchanger is incorporated in the equipment warranty will be void if filters are not fitted IMPORTANT NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE FRESH AIR INTAKE El...

Page 8: ...rd Equipment Layout Supply Air Fresh Air Dumpback Damper Forklift Supports Lifting Points Lifting Points DX Coil Filters Condensor Fan 8 OAP Outside Air Package Units Installation and Operation Manual...

Page 9: ...ring operation after the unit has stabilised Compressor Control Board TX Valve All TX valves have adjustment for super heat settings 8 11K is acceptable for R407C and R410A gases OAP Outside Air Packa...

Page 10: ...for transport and for the operation of the compressor Electrical Connection Tighten all electrical connections before starting and commissioning unit Phase Failure Relay Fan Control Card Adjust pots...

Page 11: ...eck condensate drain if applicable for free drainage Guide to How Frequency According to Usage is Established Disposable Corrugated Filters Ordinary disposable corrugated filters should last approxima...

Page 12: ...The original service call costs in identifying a warranty claim Freight and travel changes for work performed or parts supplied outside of all capital cities in Australia Field wiring refrigerant pip...

Page 13: ...t during transport Leak test all caps and screwed connections after commissioning Starting Unit Check fans and Air Flow Turn on all circuit breakers Turn on control circuit and activate fans Turn on s...

Page 14: ...Motor Amps Indoor Fan Motor Amps Boost Heater Element Amps Total Unit Amps Thermostat Settings C Thermostat Operating Correctly Y N Contactors Relays Operating Correctly Y N All Terminals Checked for...

Page 15: ...Commissioning Checklist Performance 1 Fresh Air Temperature C DB C WB 2 Supply Air Temperature C DB C WB Notes OAP Outside Air Package Units Installation and Operation Manual 2021 15...

Page 16: ...au P 03 8301 9200 109 111 Northcorp Blvd Broadmeadows Vic 3047 2021 Armcor Air Solutions reserves the right to alter products and specifications without notice and does not accept responsibility for p...

Reviews: