Page 24 of 25
507640-05
Issue 2245
80 DB / 67 WB Deg. Return
Air
Air T
emperature Entering Evaporator Coil, Degree F
COOLING
INPUT
(1000 BTU)
Pressure
65°
70°
75°
80°
85°
90°
95°
100°
105°
110°
115°
24
Suction
144
145
146
147
148
149
151
153
154
156
159
36
136
138
139
140
142
144
146
147
149
152
154
48
143
141
141
141
141
142
144
146
148
151
155
60
138
138
139
139
140
141
143
144
145
147
149
24
Liquid
232
251
270
291
312
335
358
382
407
434
461
36
242
260
279
299
321
344
369
394
422
450
480
48
238
257
277
299
321
344
368
394
420
448
476
60
247
267
288
310
333
357
381
408
434
462
491
Table 6.
Cooling Performance - HP
/ DF Models
70 Deg. F Return
Air
Air T
emperature Entering Evaporator Coil, Degree F
COOLING
INPUT
(1000 BTU)
Pressure
0
°
5
°
10
°
17
°
20
°
25
°
35
°
40
°
47
°
50
°
55
°
60
°
24
Suction
39
43
48
56
60
67
82
90
102
108
11
8
129
36
27
32
38
46
50
56
71
79
91
96
106
11
5
48
34
38
43
50
54
61
76
84
97
103
11
3
124
60
36
41
46
55
58
65
80
87
99
104
11
3
123
24
Liquid
309
304
300
299
299
301
310
317
330
336
348
362
36
284
292
300
311
316
324
341
350
363
369
378
388
48
272
278
284
294
299
308
328
339
356
364
377
392
60
326
325
326
330
332
337
352
361
374
384
397
412
Table 7.
Heating Performance - HP
/ DF Models