8

Installing and Piping the Humidifier

STEP 5:  Provide Support for Humidifier Body

Suspension from the ceiling is usually best. In all models
except 90 and 91 sizes, there are flanged holes near the top
of the humidifier body for mounting purposes. See drawing on
Page 14.

STEP 6:  Bring Steam Supply to the Manifold

as shown in

drawings at right. Be sure steam supply corresponds to
pressure stamped on humidifier. Do NOT use smaller pipe
sizes than shown in the table below for any connections. Take
steam supply line from the top of the supply main—

never

from

the side or bottom. See Steam Pipe Capacities on Page 14.

Expansion and Contraction.

With average length of supply

line, the dimension change from hot to cold should not exceed
2". Provide piping with 3 elbows to get swing to take care of
expansion and contraction.

STEP 7: Connect Manifold to Humidifier

as shown at the

left for the installation method you are using., Piping shown in
dotted lines is provided by the contractor. Unthreaded pipe,
size as per above, is used with the slip fitting on body. Do not
insert manifold or pipe more than 1.5" into body as measured
from face of manifold coupler nut. See Figure 9-1.

STEP 8:  Install Drip Leg and Armstrong Inverted Bucket
Steam Trap.

Connect to low pressure return. 

NEVER

connect

to return line carrying condensate from high pressure traps.

Table 8-1.  Basic Dimensions of Installation Methods 
Shown in Figure 5-1 and 5-2.

Humidifier Size

M

N

U

Min.

Min.

90 or DSA-90-M

-

5

3

/

8

"

10"

91 or DSA-91-M

2

5

/

8

"

5

11

/

16

"

13

1

/

4

"

92/1200 or DSA-92-M

2

3

/

4

"

8

9

/

16

"

13

1

/

4

"

93/1300 or DSA-93-M

4

3

/

8

"

8

9

/

16

"

24"

94/1400

5

5

/

8

"

12

1

/

2

"

28"

Table 8-2. Recommended Pipe Size

Humidifier Size

Supply

Strainer to

Manifold

Drip

Trap

Header to

Manifold

to Body

Leg

Piping

Strainer

Inlet

90 or DSA-90-M

1

/

2

"

1

/

2

"

1

/

2

"

1"

1

/

2

"

91 or DSA-91-M

3

/

4

"

1

/

2

"

1

/

2

"

1"

3

/

4

"

92/1200 or DSA-92-M

*

3

/

4

"

3

/

4

"

3

/

4

"

1"

3

/

4

"

93/1300 or DSA-93-M

*1

1

/

4

"

1

1

/

4

"

1

1

/

4

"

1

1

/

4

"

3

/

4

"

94/1400

2"

2"

2"

2"

3

/

4

"

*When steam supply is less than 5 psi use one pipe size larger.

Note:

Pitch supply piping to humidifier, 1/2" in 10 feet.
Drain and trap runouts exceeding 30 feet in length.
Avoid sags in piping.
Ream pipe and blow out at full steam pressure before connecting to
humidifier.

Figure 8-1.  Typical Runout at End of Header

Figure 8-2.  Long Runout

Figure 8-3.  Runout with Pressure Reducing Valve

Figure 8-4.  Single Runout to Multiple Humidifiers

Figure 8-5.  Models 93/1300 and 94/1400 High Capacity vs. Low Capacity Piping Options

Steam Supply and Condensate Drainage Piping for the

Armstrong Humidifier

Summary of Contents for AM-1000 Series

Page 1: ...alla loro taratura operativa PRODUCT DESCRIPTION PRODUKTBESCHREIBUNG DESCRIPTION DU PRODUIT DESCRIPCION DEL PRODUCTO PRODUKT OMSCHRIJVING DESCRIZIONE DEL PRODOTTO Armstrong International S A Parc Indu...

Page 2: ...twortung f r die Montage und Einstellung Pour le d pannage les m thodes de test la fr quence d entretien et la liste d taill e des pi ces de rechange veuillez vous r f rer la litt rature Armstrong ou...

Page 3: ...8 Multiple Manifolds 9 Pneumatic Piping for Air Operated Models 10 Wiring for Electrically Operated Models 11 Operation and Servicing 13 Page Table of Contents Steam humidifiers or other products shou...

Page 4: ...8 1 2 NPT 1 1 2 91 Size 511 16 2 1 1 11 4 17 8 1 2 NPT 1 3 4 92 Size 89 16 2 1 1 13 4 25 8 3 4 NPT 1 3 4 1200 Size 89 16 2 1 1 13 4 25 8 3 4 NPT 1 3 4 93 Size 91 16 2 15 8 15 8 21 8 31 8 11 4 NPT 11 4...

Page 5: ...istribution manifold into center of active air flow and as close to fan discharge as possible Fig 3 10 Always install distribution manifold as far upstream from a discharge air grille as possible neve...

Page 6: ...ngs indicated by dotted lines are furnished by installing contractor Dimensions and pipe sizes are given in Tables 8 1 and 8 2 on Page 8 Methods of Installing Humidifiers OR U Min N Min Manifold Drip...

Page 7: ...irt Pocket Trap Figure 5 2 Installation Method Where Vertical Manifold Installation is Required Dimensions and pipe sizes are given in Tables 8 1 and 8 2 on Page 8 Figure 5 1 Installation Detail for H...

Page 8: ...el 90 Union Ell Models 91 94 and 1200 1400 Manifold Manifold Escutcheon Plate Manifold Coupler Nut with Washer and O Ring Figure 6 2 Components Furnished as Part of a Standard Single Manifold Installa...

Page 9: ...93 1300 11 4 NPT 1 NPT 23 8 83 4 94 1400 2 NPT 2 NPT 31 2 10 Manifold Pipe Adaptor Steam Inlet Connection B A Steam Jacket Connection Manifold Figure 7 2 Connection size and dimensions of manifold wit...

Page 10: ...r nut See Figure 9 1 STEP 8 Install Drip Leg and Armstrong Inverted Bucket Steam Trap Connect to low pressure return NEVER connect to return line carrying condensate from high pressure traps Table 8 1...

Page 11: ...kets are not trapped separately Note The humidifier steam inlet is below the bottom manifold If the bottom manifold is below the humidifier inlet piping should be as in Figure 9 3 Note When steam supp...

Page 12: ...ns for shutdown on power failure or other system trouble Interlock should be such that the valve will go to the closed position on a system shutdown rather than be locked in its position at time of sh...

Page 13: ...ntil the humidifier reaches steam temperature Auxiliary Controls for All Models Hi Limit Duct Humidity Controller An enclosed switch type high limit humidistat is recommended in the duct at least 10 f...

Page 14: ...age Figure 12 1 Wiring diagram for BLEM or BNVEM Series Humidifiers Using Armstrong 0 10 VDC Humidistats A9023 Pressure Switch Optional Armstrong 0 10 VDC Stat A18609 or A18610 B1564 Electric Temperat...

Page 15: ...tor control so that humidifier control valve will remain closed Then A Open steam supply valve to bring humidifier up to temperature B When drain line from humidifier is at steam temperature activate...

Page 16: ...ngth In 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 11 4 52 68 97 120 140 11 2 81 100 150 180 210 2 160 210 300 370 430 21 2 270 350 500 610 710 Table 14 3 Steam Pipe Capacity at 15 psi Pressure drop psi per 1...

Page 17: ...ioned horizontally use a spirit level Manifolds longer than one foot should be supported When supporting the manifold on the far end allow for manifold expansion and contraction of 1 2 1 Continue inst...

Page 18: ...Armstrong International Inc Armstrong warrants to the original user of those products supplied by it and used in the service and in the manner for which they are intended that such products shall be...

Reviews: