background image

10

Pneumatic Piping for Air Operated Humidifier–AM Models

STEP 9A:  Install Pneumatic Piping

in accordance with Fig. 10-1 or
engineer’s layout.

a. Control Air Supply. Unless

otherwise specified, air supply for
Armstrong Humidifiers should be 20
psig maximum. This air must be
clean and dry.

b. Air Piping. 

1

¼

4

" plastic tubing or

equivalent is recommended for all
air connections.

Note:

When a pilot positioner is

furnished, it should be hooked up as
shown in Fig. 10-3.

STEP 10A: Install and Connect
Humidity Controller

as specified by

engineer in accordance with
manufacturer’s instructions. If location
is not specified it may be installed in

the area controlled or in either the
return air or exhaust air ducts.

Auxiliary Controls

Hi-Limit Duct Humidity Controller.

A

high limit humidistat is recommended
in the duct at least 10 feet
downstream from the humidifier to
override the controlling humidistat.
This high-limit humidistat automatically
prevents local saturation at the point of
steam introduction. It also prevents
overloading the duct with vapor in the
event of failure of air conditioning
system components, incorrect control
settings or tampering. See Fig. 10-1.

Interlocks for Shutdowns.

Humidifiers should be interlocked with
fans for shutdown on power failure or
other system trouble. Interlock should

be such that the valve will go to the
closed position on a system shutdown
rather than be locked in its position at
time of shutdown. See Figure 10-2.

Temperature Switch for Automatic
Warm Up.

For systems that may be

started and stopped, such as in
laboratories or in operations which
shut down each weekend, a
temperature switch is recommended
on the condensate outlet from the
humidifier. Your Armstrong
Representative can supply an
immersion type unit that will
automatically keep valves closed
during warm up period after shutdown.
This will avoid the discharge of
condensate that can occur if steam is
admitted to cold humidifier piping
when the humidifier valve is open See
Fig. 10-1.

Figure 10-1.  Standard compressed air hook-up for all pneumatically
operated humidifiers. Pneumatic temperature switch shown.

Figure 10-3.  Compressed air hook-up for humidifiers utilizing a
Honeywell MP953-F pneumatic operator with pilot positioner.

Figure 10-4.  Compressed air hook-up for humidifiers utilizing two
Armstrong Duct Humidity Controllers, one as the humidity controller, 
the other as a high limit controller.

Figure 10-2.  Compressed air hook-up for air operated humidifiers
incorporating safety interlock for shutdown in the event of power failure
to fan and an electric temperature switch to prevent water discharge on
start-up when humidifier piping is cold.

Summary of Contents for AM-1000 Series

Page 1: ...alla loro taratura operativa PRODUCT DESCRIPTION PRODUKTBESCHREIBUNG DESCRIPTION DU PRODUIT DESCRIPCION DEL PRODUCTO PRODUKT OMSCHRIJVING DESCRIZIONE DEL PRODOTTO Armstrong International S A Parc Indu...

Page 2: ...twortung f r die Montage und Einstellung Pour le d pannage les m thodes de test la fr quence d entretien et la liste d taill e des pi ces de rechange veuillez vous r f rer la litt rature Armstrong ou...

Page 3: ...8 Multiple Manifolds 9 Pneumatic Piping for Air Operated Models 10 Wiring for Electrically Operated Models 11 Operation and Servicing 13 Page Table of Contents Steam humidifiers or other products shou...

Page 4: ...8 1 2 NPT 1 1 2 91 Size 511 16 2 1 1 11 4 17 8 1 2 NPT 1 3 4 92 Size 89 16 2 1 1 13 4 25 8 3 4 NPT 1 3 4 1200 Size 89 16 2 1 1 13 4 25 8 3 4 NPT 1 3 4 93 Size 91 16 2 15 8 15 8 21 8 31 8 11 4 NPT 11 4...

Page 5: ...istribution manifold into center of active air flow and as close to fan discharge as possible Fig 3 10 Always install distribution manifold as far upstream from a discharge air grille as possible neve...

Page 6: ...ngs indicated by dotted lines are furnished by installing contractor Dimensions and pipe sizes are given in Tables 8 1 and 8 2 on Page 8 Methods of Installing Humidifiers OR U Min N Min Manifold Drip...

Page 7: ...irt Pocket Trap Figure 5 2 Installation Method Where Vertical Manifold Installation is Required Dimensions and pipe sizes are given in Tables 8 1 and 8 2 on Page 8 Figure 5 1 Installation Detail for H...

Page 8: ...el 90 Union Ell Models 91 94 and 1200 1400 Manifold Manifold Escutcheon Plate Manifold Coupler Nut with Washer and O Ring Figure 6 2 Components Furnished as Part of a Standard Single Manifold Installa...

Page 9: ...93 1300 11 4 NPT 1 NPT 23 8 83 4 94 1400 2 NPT 2 NPT 31 2 10 Manifold Pipe Adaptor Steam Inlet Connection B A Steam Jacket Connection Manifold Figure 7 2 Connection size and dimensions of manifold wit...

Page 10: ...r nut See Figure 9 1 STEP 8 Install Drip Leg and Armstrong Inverted Bucket Steam Trap Connect to low pressure return NEVER connect to return line carrying condensate from high pressure traps Table 8 1...

Page 11: ...kets are not trapped separately Note The humidifier steam inlet is below the bottom manifold If the bottom manifold is below the humidifier inlet piping should be as in Figure 9 3 Note When steam supp...

Page 12: ...ns for shutdown on power failure or other system trouble Interlock should be such that the valve will go to the closed position on a system shutdown rather than be locked in its position at time of sh...

Page 13: ...ntil the humidifier reaches steam temperature Auxiliary Controls for All Models Hi Limit Duct Humidity Controller An enclosed switch type high limit humidistat is recommended in the duct at least 10 f...

Page 14: ...age Figure 12 1 Wiring diagram for BLEM or BNVEM Series Humidifiers Using Armstrong 0 10 VDC Humidistats A9023 Pressure Switch Optional Armstrong 0 10 VDC Stat A18609 or A18610 B1564 Electric Temperat...

Page 15: ...tor control so that humidifier control valve will remain closed Then A Open steam supply valve to bring humidifier up to temperature B When drain line from humidifier is at steam temperature activate...

Page 16: ...ngth In 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 11 4 52 68 97 120 140 11 2 81 100 150 180 210 2 160 210 300 370 430 21 2 270 350 500 610 710 Table 14 3 Steam Pipe Capacity at 15 psi Pressure drop psi per 1...

Page 17: ...ioned horizontally use a spirit level Manifolds longer than one foot should be supported When supporting the manifold on the far end allow for manifold expansion and contraction of 1 2 1 Continue inst...

Page 18: ...Armstrong International Inc Armstrong warrants to the original user of those products supplied by it and used in the service and in the manner for which they are intended that such products shall be...

Reviews: