background image

4

B.  If automatic control is not used, the use of a hand 

switch to control the fan motor has de

fi

 nite ad-

vantages.  The fan operates continuously during 
the heating season.  The motors are oil less in all 
positions.  Current consumption is low – 6 watts 
for all AMEF models.

For FSA, VSA Models (See Figs. 3-4 & 3-5)

A.  Beware of Voltage Drop.  If the wire supplying 

current to the humidi

fi

 er is too small or too long, 

there may be a voltage drop that will reduce the 
life of your equipment.  When the voltage is too 
low, the solenoid valve will not open but current 
will continue to 

fl

 ow and will burn up the coil.

B.  24 Volt Wiring.  (VSA Only)

 Where codes permit 

24 volt wiring without conduit, the use of a 120-24 
volt transformer relay, as shown in Fig. 3-5 will 
lower the installation cost.

Step 7: Install Pneumatic Piping. (AM)

A. Air 

Supply.

 Air supply for Armstrong Humidi

fi

 ers 

should be 15 to 20 psi. This air must be clean and 
dry instrument air. Make air connections to fan of 
AMAF models.

B. Compressed 

Air 

Piping.

 Plastic tubing or equiva-

lent is used for all air connections.

Step 8: Install Humidity Controller.

Location. 

The humidistat should be installed anywhere 

from 20 ft. to 30 ft. from the humidi

fi

 er – at one side of 

the air stream from the humidi

fi

 er. The hygrostat should 

be able to “see” the unit controlled. It must not be hidden 
behind piles of goods or in channels of columns where air 
movements cannot reach it. It may be necessary to experi-
ment with the location in order to get the best control.

Setting and Adjusting

 should be done in accordance with 

the manufacturer’s instructions furnished with the humidi-
stat.

Recommended Option.

A pneumatic or an electric temperature switch is recom-
mended in any system where the steam supply to the 
manifold jacket and humidi

fi

 er body may be interrupted or 

turned off.

Air and Electrical Connections

Sizing and Selection

A survey of your requirements should be taken to deter-
mine the amount of steam needed for humidi

fi

 cation, the 

number, size and type of units required, and the location of 
both humidi

fi

 er and humidity controllers.

Sizing and location with natural ventilation.

These are the average industrial humidi

fi

 cation applications 

with:

Room temperatures – 65° to 80°.

Relative humidities – 35% to 80%.

Natural ventilation – i.e., in

fi

 ltration around windows and 

doors.

Selection Data Required.

  Minimum Outdoor Temperature: for most jobs, 

fi

 gure  

  10°F above the lowest recorded temperature for your  
  locality. The lowest temperatures are seldom  

 

  encountered for more than a few hours. 

 Indoor Temperature

 RH Desired

  Pressure of Steam Available for Humidi

fi

 cation

  Number of Cubic Feet in Room

  Air Changes Per Hour: air changes taking place under  

  average conditions exclusive of air provided for  

 

  ventilation or regain of hygroscopic materials.

Rooms, 1 side exposed ................... 1
Rooms, 2 sides exposed .................  1 ½
Room, 3 or 4 sides exposed ............ 2
Rooms with no windows or 
 

outside doors ............................  ½ - ¾

Typical Problem:

Design outdoor temperature ............ 0°F
Indoor temperature .......................... 70°F
RH required ..................................... 40%
Air changes per hour ....................... 2
Steam pressure available ................ 5 psi
Room size 400’ x 160’ with 10’ ceiling.
Natural ventilation
Heated by:
      Unit heaters – fan on-off control.

Step 1:

 Steam required for humidi

fi

 cation. Our room con-

tains (400’ x 160’ x 10’) or 640,000 cu. Ft.

From the 70°F Table 5-1, read across from 0°F outside 
temperature to the 40% RH column where you 

fi

 nd the 

fi

 gure .409 lbs. of steam per hour per 1000 cu. ft. of space 

for each air change. Then, 640 x .409 x 2 equals 524 lbs. of 
steam per hour installed humidi

fi

 cation capacity required.

Step 2:

 Electric or air controlled units. The large 

fl

 oor area 

calls for multiple humidi

fi

 ers. No explosion hazard has 

been speci

fi

 ed so use of air controlled units is not required. 

Electric units are recommended.

Step 3:

 Number of humidi

fi

 ers for job. Divide steam 

required by capacity of humidi

fi

 ers at steam pressure avail-

able.

Step 4:

 What size humidi

fi

 er to use. For this example, a 

large number of smaller capacity units is recommended. 
Larger capacity units could cause condensation on the low 
ceiling. Also, because of the large 

fl

 oor area, the humidi-

stats for fewer units would be widely spaced, which could 
result in less accurate control than desirable.

Summary of Contents for AM-91A

Page 1: ...spring range is specified AM VSA Models AMEF AMAF FSA Models Figure 1 1 Figure 1 2 Dimensions Armstrong Area Humidifiers Fig 1 1 VSA AM models do not have fans Fig 1 2 FSA AMEF models have electrically operated fans AMAF models utilize air powered fans Installation Procedure B C D F J E H G C D F B J E Table 1 1 Model No B C D E F G H J AM 91A 15 15 16 3 3 8 3 13 16 6 1 16 3 1 16 13 1 4 AMAF 91A 1...

Page 2: ...1 1 4 1 1 4 1 1 4 3 4 Steam Pipe Capacities For computing ability of piping to deliver an adequate supply of steam to humidifier Capacities shown are in pounds per hour Table 2 2 Steam Pipe Capacity at 5 psi Pipe Size in Pressure drop psi per 100 ft of pipe length 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 1 1 4 52 68 97 120 140 1 1 2 81 100 150 180 210 2 160 210 300 370 430 2 1 2 270 350 500 610 710 Tabl...

Page 3: ...ve Relief Valve A pressure relief valve between the humidifier and pressure reducing valve is a good insurance Humidi fier bodies are only rated for 60 psig steam service Pressure Gage A pressure gage or connection for install ing a gage between reducing valve and the humidifier may save its cost many times over Air and Electrical Connections 10 Min Strainer Steam Trap Steam Trap Steam Supply Dirt...

Page 4: ...r size and type of units required and the location of both humidifier and humidity controllers Sizing and location with natural ventilation These are the average industrial humidification applications with Room temperatures 65 to 80 Relative humidities 35 to 80 Natural ventilation i e infiltration around windows and doors Selection Data Required Minimum Outdoor Temperature for most jobs figure 10 ...

Page 5: ...ges These can be determined from exhaust fan capacity where known The cu ft per hour capacity of the fans divided by the cubic feet of space to be humidified will give the number of air changes Where the capacity of fan or fans is not known air changes can be measured with velometer readings at all open doors elevator shafts etc leading to the room and with fans operating at full capacity Your Arm...

Page 6: ...on is through a jet nozzle or by a fan How air operated units work Air operated units operate in the same manner as electric units except that they Operation Figure 6 1 utilize a pneumatic humidistat as humidity controller in the space and an air operator to open and close the steam valve Explosion hazard humidification Sizing air operated humidifiers for areas where an explosion hazard ex ists is...

Page 7: ...with dirt 2 Return line pressure above humidifier pressure 3 Too much vertical lift 4 Wrong type of trap used 5 Second trap short circuiting the humidifier trap Operation and Servicing Humidifier Discharges Continuously Even though Humidity Has Reached Desired Level A Mechanical Trouble 1 Humidistat fails to open points frozen 2 Dirt holds solenoid plunger in open position 3 Bent solenoid tube hol...

Page 8: ...efects or any condition or use of the products supplied by Armstrong however caused and whether such claim is based upon warranty contract negligence strict liability or any other basis or theory is limited to Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase...

Reviews: