background image

5

Step 5:

 What type of humidi

fi

 er to use. In this example, in-

tegral fan units are preferable to steam jet units installed in 
conjunction with unit heaters. Since the unit heater fans are 
on or off to control temperature, it follows that the humidi-
stat may call for steam when the nearest unit heater is nor 
running. With the low ceiling, the discharge from a steam 
jet humidi

fi

 er might rise to the ceiling and produce conden-

sation. Therefore, the integral fan type should be used.

Step 6

: Location of humidi

fi

 ers. Several patterns are pos-

sible, and actual location can usually conform with the ex-
isting steam supply and return lines to make an economical 
installation with a minimum of new piping.

In our problem of a 400’ x 160’ x 10’ room, there would 
likely be steam lines along both sides of the room, and 
humidi

fi

 ers can be located as shown in Fig. 5-1. If the sup-

ply lines run down the center of the room, the center line 
pattern would be practical. Runouts to integral fan units 
in a 160’ wide room would be about 20’ long. If the room 
were only 60 or 80 ft. wide, runouts need be no longer than 
required for actual hook-up.

Step 7:

 Location of humidistat. This should be form 20 to 

30 feet away from the humidi

fi

 er and slightly to one side of 

the air stream from the unit. The humidistat should “see” its 
humidi

fi

 er. Do not hide it behind a post or in the channel of 

an H-beam. It must get a good sample of the air, to control 
the humidity. 

Sizing and location with forced ventilation.

Typical jobs:

 Mill and sanding rooms in furniture factories. 

Here, the problem of selecting and installing humidi

fi

 ers is 

much the same as previously described except for:

A.  Determining the number of air changes.

B.  Location of humidi

fi

 ers and humidistat.

Air Changes:

 These can be determined from exhaust fan 

capacity where known. The cu. ft. per hour capacity of the 
fans divided by the cubic feet of space to be humidi

fi

 ed will 

give the number of air changes.

Where the capacity of fan or fans is not known, air changes 
can be measured with velometer readings at all open 
doors, elevator shafts, etc., leading to the room and with 
fans operating at full capacity. Your Armstrong Representa-
tive can determine air changes for you. 

Humidifi er Location:

 Bear in mind that humidi

fi

 ers will 

have to control the humidity 24 hours a day, seven days a 
week during the heating season. Exhaust fans may operate 
only 40 hours or 80 hours per week. Thus the humidi

fi

 ers 

and humidistats must be located for good distribution of 
humidity during the fan-off periods as well as when the fans 
are operating. Figure 5-2 outlines a typical requirement.

Sizing and Selection

Figure 5-1.

Figure 5-2.

Where practical, locate humidifiers to minimize
piping.  Locations shown where steam supply
lines are along outer walls; and where supply
is in center of room.

Schematic layout of humidifiers in woodworking plant
where exhaust fans are used. Arrows indicate air flow
induced by fans. Humidifiers are sized for load conditions
imposed by fan. Humidifiers are located to give uniform
distribution of humidity when fans are off or when fans
are running.

  Table 5-1

70°F. Humidifi cation. Pounds of Steam Per Hour, Per Air Chcange for Each 1000 cu. FT. of Space to Secure Desired Indoor Relative 
Humidity at 70°F. with Various Outdoor Temperature (Outside Air 75% Saturated).

Outdoor

Temp.

70°F. - RELATIVE HUMIDITY DESIRED INDOORS-70°F

25%

30%

35%

40%

45%

50%

55%

60%

65%

70%

75%

30

.079

.136

.194

.251

.309

.367

.424

.482

.539

.597

.654

20

.154

.212

.269

.327

.385

.441

.499

.557

.615

.672

.730

10

.204

.262

.319

.377

.434

.492

.549

.607

.665

.722

.780

0

.237

.294

.352

.409

.467

.524

.582

.639

.697

.754

.812

-10

.257

.314

.372

.430

.487

.545

.602

.660

.717

.775

.832

-20

.270

.327

.385

.442

.500

.557

.615

.672

.730

.787

.844

Summary of Contents for AM-91A

Page 1: ...spring range is specified AM VSA Models AMEF AMAF FSA Models Figure 1 1 Figure 1 2 Dimensions Armstrong Area Humidifiers Fig 1 1 VSA AM models do not have fans Fig 1 2 FSA AMEF models have electrically operated fans AMAF models utilize air powered fans Installation Procedure B C D F J E H G C D F B J E Table 1 1 Model No B C D E F G H J AM 91A 15 15 16 3 3 8 3 13 16 6 1 16 3 1 16 13 1 4 AMAF 91A 1...

Page 2: ...1 1 4 1 1 4 1 1 4 3 4 Steam Pipe Capacities For computing ability of piping to deliver an adequate supply of steam to humidifier Capacities shown are in pounds per hour Table 2 2 Steam Pipe Capacity at 5 psi Pipe Size in Pressure drop psi per 100 ft of pipe length 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 1 1 4 52 68 97 120 140 1 1 2 81 100 150 180 210 2 160 210 300 370 430 2 1 2 270 350 500 610 710 Tabl...

Page 3: ...ve Relief Valve A pressure relief valve between the humidifier and pressure reducing valve is a good insurance Humidi fier bodies are only rated for 60 psig steam service Pressure Gage A pressure gage or connection for install ing a gage between reducing valve and the humidifier may save its cost many times over Air and Electrical Connections 10 Min Strainer Steam Trap Steam Trap Steam Supply Dirt...

Page 4: ...r size and type of units required and the location of both humidifier and humidity controllers Sizing and location with natural ventilation These are the average industrial humidification applications with Room temperatures 65 to 80 Relative humidities 35 to 80 Natural ventilation i e infiltration around windows and doors Selection Data Required Minimum Outdoor Temperature for most jobs figure 10 ...

Page 5: ...ges These can be determined from exhaust fan capacity where known The cu ft per hour capacity of the fans divided by the cubic feet of space to be humidified will give the number of air changes Where the capacity of fan or fans is not known air changes can be measured with velometer readings at all open doors elevator shafts etc leading to the room and with fans operating at full capacity Your Arm...

Page 6: ...on is through a jet nozzle or by a fan How air operated units work Air operated units operate in the same manner as electric units except that they Operation Figure 6 1 utilize a pneumatic humidistat as humidity controller in the space and an air operator to open and close the steam valve Explosion hazard humidification Sizing air operated humidifiers for areas where an explosion hazard ex ists is...

Page 7: ...with dirt 2 Return line pressure above humidifier pressure 3 Too much vertical lift 4 Wrong type of trap used 5 Second trap short circuiting the humidifier trap Operation and Servicing Humidifier Discharges Continuously Even though Humidity Has Reached Desired Level A Mechanical Trouble 1 Humidistat fails to open points frozen 2 Dirt holds solenoid plunger in open position 3 Bent solenoid tube hol...

Page 8: ...efects or any condition or use of the products supplied by Armstrong however caused and whether such claim is based upon warranty contract negligence strict liability or any other basis or theory is limited to Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase...

Reviews: