background image

6

How electrically operated units work.

After passing through the Armstrong inline 
strainer, steam enters the cast iron steam-
separating chamber. The use of cast iron 
as a separator is probably the single most 
important feature in the Armstrong humidi-

fi

 er design.

The preferred material of strength and 
durability, case iron gives Series 9000 
humidi

fi

 ers 

fl

 exibility in design without 

fabrication. In addition, castings mean 
better heat retention because of thicker 
walls. Which in turn means a lower rate of 
condensation.

Entering the main separating chamber, 
steam encounters a cupped baf

fl

 e which 

reverses its 

fl

 ow and turns it back on itself. 

The outer walls of the casting form another 
cup, and the same thing happens again. 
These two 180° turns help condition the 
steam, reducing its volume and separating 
the condensate from the vapor. Conden-
sate from supply and radiation and most of 
the particulates in the steam not removed 
by the strainer collect in the large drain leg 
and are discharged through the inverted 
bucket drain trap.

Steam from the separating chamber 

fl

 ows 

around and through the solenoid valve 
which is actuated by a demand signal from 
the humidistat. (Solenoid can be ex-
changed for electric or pneumatic control 
if desired by choosing an operator and 
bonnet assembly).

Next the steam 

fl

 ows into the drying cham-

ber which is jacketed by the separating 
chamber. The drying chamber is 

fi

 lled with 

a stainless steel silencing material which 
almost completely absorbs the noise of 
escaping steam. Dispersion is through a 
jet nozzle or by a fan.

How air-operated units work.

Air-operated units operate in the same 
manner as electric units except that they 

Operation

Figure  6-1.

utilize a pneumatic humidistat as humidity controller in the space and an 
air operator to open and close the steam valve.

Explosion hazard humidifi cation.

Sizing air-operated humidi

fi

 ers for areas where an explosion hazard ex-

ists is done exactly as for other requirements except that they should be 
sized for the 

most severe

 conditions of makeup air, RH required and 

minimum steam pressure.

Table 6-1

75°F. Humidifi cation. Pounds of Steam Required Per Hour, Per Air Chcange for Each 1000 cu. FT. of Space to Secure Desired Indoor Relative 
Humidity at 75°F. with Various Outdoor Temperature (Outside Air 75% Saturated).

Outdoor 

Temp.

70°F. - RELATIVE HUMIDITY DESIRED INDOORS-70°F

25%

30%

35%

40%

45%

50%

55%

60%

65%

70%

75%

30

.129

.196

.264

.331

.399

.466

.533

.601

.668

.736

.803

20

.204

.271

.339

.406

.474

.541

.609

.676

.744

.811

.879

10

.254

.321

.389

.456

.524

.591

.659

.726

.794

.861

.929

0

.286

.354

.421

.489

.556

.624

.691

.759

.826

.894

.961

-10

.307

.374

.442

.509

.577

.644

.711

.779

.846

.914

.981

-20

.319

.387

.454

.522

.589

.657

.724

.792

.859

.927

.994

Strainer

Fan

Solenoid Valve Open

Humidistat

Switch

Separating
Chamber

Drying
Chamber

Temperature
Switch

Baffle

Steam

Trap

Steam
Supply

Condensate

Steam at 
Atmospheric Pressure

Steam at
Supply Pressure

  Table 6-2 Location of Unit Humidifi ers for Direct Discharge into Atmosphere.

Method of Steam 

Dispersion

Maximum Discharge 

Capacities in lbs. of 

Steam per hour

Minimum 

Ceiling

Ceiling 

Clearance

30

8’

2’

Electric Fan

80

10’

3’

FSA, AMEF Models

200

14’

6’

300

16’

8’

30

10’

3’

Air Fan

80

12’

4’

AMAF Models

200

16’

8’

300

20’

8’

30

10’

4’

Jet

80

12’

6’

VSA, AM Models

200

20’

10’

300

20’

10’

Summary of Contents for AM-91A

Page 1: ...spring range is specified AM VSA Models AMEF AMAF FSA Models Figure 1 1 Figure 1 2 Dimensions Armstrong Area Humidifiers Fig 1 1 VSA AM models do not have fans Fig 1 2 FSA AMEF models have electrically operated fans AMAF models utilize air powered fans Installation Procedure B C D F J E H G C D F B J E Table 1 1 Model No B C D E F G H J AM 91A 15 15 16 3 3 8 3 13 16 6 1 16 3 1 16 13 1 4 AMAF 91A 1...

Page 2: ...1 1 4 1 1 4 1 1 4 3 4 Steam Pipe Capacities For computing ability of piping to deliver an adequate supply of steam to humidifier Capacities shown are in pounds per hour Table 2 2 Steam Pipe Capacity at 5 psi Pipe Size in Pressure drop psi per 100 ft of pipe length 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 1 1 4 52 68 97 120 140 1 1 2 81 100 150 180 210 2 160 210 300 370 430 2 1 2 270 350 500 610 710 Tabl...

Page 3: ...ve Relief Valve A pressure relief valve between the humidifier and pressure reducing valve is a good insurance Humidi fier bodies are only rated for 60 psig steam service Pressure Gage A pressure gage or connection for install ing a gage between reducing valve and the humidifier may save its cost many times over Air and Electrical Connections 10 Min Strainer Steam Trap Steam Trap Steam Supply Dirt...

Page 4: ...r size and type of units required and the location of both humidifier and humidity controllers Sizing and location with natural ventilation These are the average industrial humidification applications with Room temperatures 65 to 80 Relative humidities 35 to 80 Natural ventilation i e infiltration around windows and doors Selection Data Required Minimum Outdoor Temperature for most jobs figure 10 ...

Page 5: ...ges These can be determined from exhaust fan capacity where known The cu ft per hour capacity of the fans divided by the cubic feet of space to be humidified will give the number of air changes Where the capacity of fan or fans is not known air changes can be measured with velometer readings at all open doors elevator shafts etc leading to the room and with fans operating at full capacity Your Arm...

Page 6: ...on is through a jet nozzle or by a fan How air operated units work Air operated units operate in the same manner as electric units except that they Operation Figure 6 1 utilize a pneumatic humidistat as humidity controller in the space and an air operator to open and close the steam valve Explosion hazard humidification Sizing air operated humidifiers for areas where an explosion hazard ex ists is...

Page 7: ...with dirt 2 Return line pressure above humidifier pressure 3 Too much vertical lift 4 Wrong type of trap used 5 Second trap short circuiting the humidifier trap Operation and Servicing Humidifier Discharges Continuously Even though Humidity Has Reached Desired Level A Mechanical Trouble 1 Humidistat fails to open points frozen 2 Dirt holds solenoid plunger in open position 3 Bent solenoid tube hol...

Page 8: ...efects or any condition or use of the products supplied by Armstrong however caused and whether such claim is based upon warranty contract negligence strict liability or any other basis or theory is limited to Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase...

Reviews: