28
Output
Three Phase
lbs/hr
kg/hr
208
240
380
480
600
Amp
kW
Amp
kW
Amp
kW
Amp
kW
Amp
kW
EHU 801 (One small generator)
6
3
6.3
2.3
5.4
2.3
11
5
10.4
3.8
9.0
3.8
5.7
3.8
4.5
3.8
3.6
3.8
17
8
16.7
6.0
14.5
6.0
9.1
6.0
7.2
6.0
5.8
6.0
22
10
20.9
7.5
18.1
7.5
11.4
7.5
9.0
7.5
7.2
7.5
33
15
17.1
11.3
13.6
11.3
10.9
11.3
44
20
22.8
15.0
18.1
15.0
14.5
15.0
EHU 803 (one large steam generator)
33
15
31.3
11.3
27.1
11.3
44
20
41.7
15.0
36.2
15.0
55
25
45.2
18.8
28.6
18.8
22.6
18.8
18.1
18.8
66
30
34.3
22.6
27.1
22.6
21.7
22.6
77
35
40.0
26.3
31.7
26.3
25.3
26.3
88
40
45.7
30.1
36.2
30.1
28.9
30.1
99
45
40.7
33.8
32.6
33.8
110
50
45.2
37.6
36.2
37.6
EHU 804 (two large steam generators)
55
25
52.2
18.8
66
30
62.6
22.6
54.3
22.6
77
35
73.0
26.3
63.3
26.3
88
40
83.5
30.1
72.3
30.1
99
45
93.9
33.8
81.4
33.8
51.4
33.8
110
50
90.4
37.6
57.1
37.6
121
55
62.8
41.4
49.7
41.4
39.8
41.4
132
60
68.5
45.1
54.3
45.1
43.4
45.1
143
65
74.3
48.9
58.8
48.9
47.0
48.9
154
70
80.0
52.6
63.3
52.6
50.6
52.6
165
75
85.7
56.4
67.8
56.4
54.3
56.4
176
80
91.4
60.2
72.3
60.2
57.9
60.2
187
85
76.9
63.9
61.5
63.9
198
90
81.4
67.7
65.1
67.7
209
95
85.9
71.4
68.7
71.4
220
100
90.4
75.2
72.3
75.2
231
105
95.0
78.9
76
78.9
242
110
79.6
82.7
Recommended Branch Circuits
Rating Amp
1-12
13-15
16-20
21-24
25-32
33-40
41-48
49-64
68-80
81-100
101-120
Wire
(AWG)
14
12
10
10
8
8
6
4
3
1
0
(mm2)
3
4
6
6
10
10
16
25
35
50
50
Circuit Breaker
15
20
25
30
40
50
60
80
100
125
150