20
Chemical parameters
Acrylamide
≤ 0,1μg/l
Epichlorohydrin (1)
≤ 0,1 μg/l
Aluminium
<200 μg/l
Fluoride (1)
≤ 1,5 mg/l
Ammonium (1)
< 0,1 mg/l
Iron total (1)
≤ 200 μg/l
Antimony (1)
≤ 5,0μg/l
Lead (1)
≤ 10 μg/l
Arsenic (1)
≤ 10μg/l
Magnesium (3)
≤ 50 mg
Benzene (1)
≤ 1,0 μg/l
Manganese (1)
≤ 50 μg/l
Benzo(a)pyrene (1)
≤ 0,01μg/l
Mercury (1)
≤ 1,0 μg/l
Boron (1)
≤ 1,0 mg/l
Nickel (1)
≤ 20 μg/l
Bromate (1)
≤ 10 μg/l
Nitrate (1)
≤ 50 mg/l
Cadmium (1)
≤ 5,0 μg/l
Nitrite (1)
≤ 0,50 mg/l
Calcium (3)
≤ 300 mg/l
pH (Hydrogen ion concen-
tration) (1)
6.5 to 9
Total organique carbone
(TOC) (1)
≤ 2,0 mg/l
Pesticides total (1)
≤ 0,50 μg/l
Chloride (1)
≤ 250 mg/l
Polycyclic aromatic hydro-
carbons (1)
≤ 0,10 μg/l
Chromium (1)
≤ 50 μg/l
Selenium (1)
≤10 μg/l
Conductivity (1) (3)
≤ 1000 μS/cm at 20ºC
Silicate
< 150 mg/l
Copper (1)
≤ 1,0 mg/l
Sodium
≤ 200 mg/l
Cyanide (1)
≤ 50 μg/l
Sulfate
≤ 250 mg/l
1,2-dichloroethane (1)
≤ 3,0 μg/l
Trihalomethane Total (1)
≤ 100 μg/l
Tetra- and tri-chloroethene
(1)
≤ 10 μg/l
Vinyl chloride (1)
≤ 0,50 μg/l
Radioactivity
Tritium (1)
<100 Bq/l
Total indicative dose (1)
< 0,1 mSv/year
(1)
Value given by Directive 98/83/CE
(2)
Value given by VDI 6022-4.3.7 for recirculating water in air humidifiers.
(3)
Water hardness range will be confirmed by PSI value (please see EvaPack™ bleed-off chapter)
(4)
EvaPack™ air evaporative humidifier must operate within these specifications.
These values are to be taken into account when setting the bleed-off limits.
*A too low water temperature can impact humidification efficiency.