27
The drain must be equipped with a siphon with non-return valve or a siphon disconnected from the sewage
network.
H min. (mm) = P (Pa)/10
with P = absolute pressure of the AHU/Duct
Siphon by positive pressure
Siphon by negative pressure
2H
H
2H
H
NOTES:
The drain valve has to be protected from impacts, humidity and light. The overflow piping outlet must be
always free.
Water draining installation example with a water inlet purge.
NOTE:
In case of power shutdown, the water basin must be drained manually using the manual draining valve option.
Water bassin filling valve
Supply water draining valve
Filters
Supply water