background image

5

General Safety Information

GENERAL

This manual contains all the details concerning the commissioning, operation and maintenance 

of the ExpressPack®.

Maintenance, service, repairs, as well as the study of the risks and dangers associated with 

these operations must be carried out by qualified, competent and authorized personnel.

- Make sure that all risks or dangers are defined beforehand by an authorized person, especially 

for works-at-height.

- We also recommend installing a security perimeter.

- Make sure that the steam output of the humidifier is turned off before any maintenance.

- Please screw periodically all the connection terminals of the power cable.

INTENDED USE

The ExpressPack® manufactured by Armstrong - Devatec is intended solely for humidification 

purpose, in air treatment station or in air flow. The user undertakes to use it according to the 

safety instructions given in this manual.

Improper use could result in serious hazards and damages to the user, third parties and ma

-

terials.

STORAGE 

The device must be stored in a dry, frost-free place, protected from shocks and vibrations.

WARRANTY

The group Armstrong International S.A., guarantees that its devices are 

one (1) year

 warranty. 

Armstrong’s liability will be limited exclusively to Armstrong’s repair or replacement of the part 

or product, excluding labor, disassembly or installation costs. Armstrong may also decide to 

refund the purchase price of the product or part of it, at its discretion. The non-compliance of 

these above recommendations, additional mounting and/or transformation with components 

other than those provided with the device or any use other than what is explicitly stated, shall 

be considered as not in compliance with the prescriptions, and will invalidate the warranty. 

LIABILITY

Armstrong shall be not made liable for the consequences of incorrect installation, improper use 

of the devices and/or their components.

We are committed to provide you the most complete manual, although, in the air treatment 

field, variations are so common that the information found in this document may be subject to 

changes without notice.

Summary of Contents for ExpressPack

Page 1: ...ExpressPack Installation and Operation Manual...

Page 2: ......

Page 3: ...Armstrong Contents General Safety Information 4 Product Information 6 Product Installation 7 Options 12 Troubleshooting 13 Limited Warranty and Remedy 14...

Page 4: ...t it If your package is damaged or missing please make a complaint to your carrier with a receipt acknowledgment letter within 24 hours and make a declaration to your Armstrong agent Pictures graphics...

Page 5: ...to the user third parties and ma terials STORAGE The device must be stored in a dry frost free place protected from shocks and vibrations WARRANTY The group Armstrong International S A guarantees tha...

Page 6: ...y dispersed over the whole evaporization area MATERIAL the header and dispersion tubes of our ExpressPack are made in stainless steel The grommets are made in elastomer NOZZLES each tube includes two...

Page 7: ...adapts perfectly to high air speeds Maximum speed 15 m s The header is equipped with a 13 mm outlet which ensures optimum condensate evacuation Figure 2 2D front view side view Do s Don ts of Locatio...

Page 8: ...of 5 x D between the device and the ExpressPack D being the absorption distance Figure 3 6 All airflow must be directed through ExpressPack If ExpressPack is smaller than the duct cross section Expres...

Page 9: ...to the weight of the installation by using a U shaped support bracket mounting rails Water seal for condensate drain In order to avoid any water spitting or steam leakage problem make sure that there...

Page 10: ...umidifier technical manual Piping For the steam pipe installation according to your environment respect the recommen dations below and use suitable clamps Flexible steam hose 40 or 60 mm length 3 m ma...

Page 11: ...ure 6 1 Plug grommet Figure 6 2 Standard grommet Assembly Process If the ExpressPack is delivered disassembled please follow the steps listed below to assemble it 1 Place the header of the ExpressPack...

Page 12: ...ect the steam before it s dispersed by the ExpressPack Figure 7 Flanged steam supply manifold By using a flanged steam supply manifold you can connect between 3 and 8 steam inlets Remember to choose t...

Page 13: ...over from the steam generator 2 Low or no steam output The causes can be A Incorrect realization of the siphon steam blows through See chapter Water seal for conden sate drain page 9 B High static pr...

Page 14: ...respect to any other claim relating to the products or to defects or any condition or use of the products supplied by Armstrong however caused and whether such claim is based upon warranty contract n...

Page 15: ......

Page 16: ...Rev 3 Printed in Europe 2019 01 2019 Armstrong International SA...

Reviews:

Related manuals for ExpressPack