7
Product Installation
Used only in the case of a horizontal air flow, the collector must be placed horizontally, while the
dispersion tubes must be placed vertically. The ExpressPack® can be located in the air handling
unit or inside the duct.
For more convenience, we recommend you to install the ExpressPack® near the duct access.
Please minimize the distance between the humidifier outlet and the steam inlet of the Ex
-
pressPack® (see page 10).
Thanks to the steam injection nozzles, perpendicular to the air flow, the ExpressPack® adapts
perfectly to high air speeds (Maximum speed: 15 m/s).
The header is equipped with a Ø13 mm outlet which ensures optimum condensate evacuation.
Figure 2.
2D front view / side view
Do.s & Don.ts of Location and Installation
All recommendations for the application of the Armstrong ExpressPack® are based on tests and
field experience, observed with the most common operating conditions. For this reason, these
recommendations may differ depending on variations in air speed and temperature. We also
reserve the right to modify recommendations without notice if subsequent tests or experiences
indicate that a change should be made.
See figures from 3-1 to 3-7 (page 8).
In case of doubt, do not hesitate to contact your Armstrong agent.