The outdoor air source can be a connection outside the building or a connection to an outdoor air plenum
inside the building. If the inlet combustion air is to be drawn in from a connection outside the building, special
precautions must be made, such as proper termination outside the wall, and a screen on the air inlet to
prevent any debris from entering the air inlet pipe.
The GFH-150 will require a 4” x 2” Tee to be installed on the supplied 2” section of PVC pipe, then 4” PVC /
CPVC for the inlet air pipe.
The GFH-300 and GFH-450 will come shipped with a 4” PVC connection for the supply air pipe to be
connected.
See Figure 11-1 and 11-2 below for further detail.
Figure 11-1
* Refer to special Sealed Combustion Package Venting Requirements on Page 14.
GFH-150
One Burner
GFH-300
Two Burner
GFH-450
Three Burner
Tubing 2" x 7"
A22429
Tubing 2" x 7"
A22429
Tubing 2" x 7"
A22429
Coupler B6733
Tee A22431
Tee A22431
Tee A22431
Tubing 4" x 9.5" Long
A22430
Tubing 4" x 9.5" Long
A22430
Coupler B6733
Coupler B6733
13.25
13.25
Vane S-Assy
B6893
Figure 11-2