2 WATER LEVEL DROPPED BELOW LOW LEVEL
- - The low level switch has not closed after 5
minutes of fill valve on time. This is only after initial start-up fill and boil-down sequence.
Check:
debris in water switch canister, defective fill valve, no water flow or low water pressure, drain
valve stuck open, defective low water level switch (electrodes need to be cleaned).
3 WATER LEVEL ABOVE HIGH LEVEL TIME OUT
- - The high water switch is still closed 5 minutes
after the fill valve has turned off upon hitting the high water level and a 30 second drain does not drop
the water below the high water level.
Check:
defective high water level switch, debris in level canister,
fill valve stuck open, drain valve is defective or scale buildup in drain line.
4 ILLEGAL LEVEL SWITCH STATE
- - The high level switch is closed and the low level switch is
open.
Check:
defective level switch(es), debris in electrode level canister, scale on electrodes or can-
ister, improper wiring of electrodes or float switches.
5 OVER TEMPERATURE
- - Internal temperature exceeds safe level.
Check:
low water in tank,
scale buildup on Thermocouple heating element surface, defective Thermocouple. See Clearing
"Error" Codes section.
6 WATER LEVEL HAS NOT DROPPED BELOW LOW LEVEL
- - The low water level switch has not
opened after a complete drain. Unit drains frequency and duration can be set in menu.
Check:
defec-
tive low water level switch or electrodes, defective drain valve, debris on low water level float switch or
electrodes, tank drain screen, or in drain valve
Clearing "ERROR" codes
After correcting the problem, the error state must be cleared by depressing the button "Error Clearing".
Confirm the operation, the unit should resume normal operation (If the water level is above the low
water, the unit will drain below the low water level and refill before energizing the contactor). Turning
the power on and off will not clear the error condition.
Safety Switches
When the high limit or air proving (pressure) switch opens the state light will flash green and the
message “High Humidity/Sail Switch Circuit is Open” will be shown on the front display. This is a soft
error, it does not have to be reset. When the circuit closes the unit will go back to normal operation.
27
Summary of Contents for HumidiClean HC-6100 Series
Page 28: ...HC6100 Wye Wiring layout 28...
Page 29: ...HC6100 Delta Wiring layout 29...
Page 30: ...30 HC6100 PAR Single Phase Wiring Layout...
Page 31: ...HC6300 Wye Wiring layout 31...
Page 32: ...HC6300 Delta Wiring layout 32...
Page 33: ...HC6500 Wye Wiring layout 33...
Page 34: ...HC6500 Delta Wiring layout 34...
Page 35: ...35 HC6500 WYE 2 contactors Wiring Layout...
Page 36: ...36 HC6500 Delta 2 contactors Wiring Layout...
Page 37: ...HC6700 Wye Wiring layout 37...