Procedure of HC6000 Version 7 Soft Refresh
This section is used for HC6000 software reprogramming only. Please follow the instructions carefully,
or pc board could become un-functional.
1. Install the driver program for Atmel MCU, SAM-BA on your computer first. The link for the Atmel
program AT91-ISP.exe and the latest version of can be found at the following location:
www.armstronginternational.com/hc6000refresh
2. Before refreshing the code, the old code in CPU must be erased:
a. Turn off the power supply from the breaker, and push the emergency stop button in.
b. Put Dip Switch S4-3 in the on position (Test Mode Select), turn on the breaker and pull out
emergency button. The indicator LED D47 on main board will remain ON. Keep the power
supply on for at least 8 seconds.
(This is the step to erase the old code.)
c. Turn off the power supply and put dip switch S4-3 to the off position.
d. Turn on the power supply, the indicator LED D47 will remain ON.
3. Loading the new code:
a. Connect the main board to computer with an USB cable. The computer should find the new
hardware, "ATMEL AT91xxxxx Test Board "and install driver for board automatically. If system
can not find the board automatically, please install driver manual, the path of the install file
.inf is:
c:/wingdows/info/atm6124.inf
b. Run program SAM-BA select the connection port as "\usb\ARM0", select board as
AT91SAM7S256-EK", please see figure 1 below.
Fig.1 SAM-BA Start Up Window
c. Click "Connect" button to enter the download window. Please see figure 2 on page 43.
43
Summary of Contents for HumidiClean HC-6100 Series
Page 28: ...HC6100 Wye Wiring layout 28...
Page 29: ...HC6100 Delta Wiring layout 29...
Page 30: ...30 HC6100 PAR Single Phase Wiring Layout...
Page 31: ...HC6300 Wye Wiring layout 31...
Page 32: ...HC6300 Delta Wiring layout 32...
Page 33: ...HC6500 Wye Wiring layout 33...
Page 34: ...HC6500 Delta Wiring layout 34...
Page 35: ...35 HC6500 WYE 2 contactors Wiring Layout...
Page 36: ...36 HC6500 Delta 2 contactors Wiring Layout...
Page 37: ...HC6700 Wye Wiring layout 37...