Drainage
Connect HC-6000 drain to suitable waste drainage
system. HC-6000 drain water may be as hot as 70°C
(158°F). Use clear drain hose provided and 25 mm (1”)
copper pipe pitched away from unit at 25 mm (1”)
inch per foot. An air gap to prevent back flow is required.
See Figure 7-1.
7
1-12
13-15
16-20
21-24
25-32
33-40
41-48
49-64
68-80
81-100
101-120
121-140
141-60
(AWG)
14
12
10
10
8
8
6
4
3
1
0
0
0
(mm2)
3
4
6
6
10
10
16
25
35
50
50
70
95
15
20
25
30
40
50
60
80
100
125
150
175
200
Table 7-1. Recommended Branch Circuits
Rating Amp
Wire
Circuit Breaker
Nominal
Amperage
Rating
Nominal
Amperage
Rating
Nominal
Amperage
Rating
Single
Three
Single
Three
208
13.3
7.7
3.8 (8.3)
39
23
11 (24)
37
18 (40)
46
22 (48)
74
36 (80)
240
12.9
7.5
38
22
36
44
72
400
—
4.7
—
14
23
28
46
480
—
3.8
—
11
18
22
36
600
—
3
—
9
15
18
30
HC6100/HC6100DI
HC6300/HC6300DI
Table 7-2. Steam Capacities and Rating Amperages
Nominal
Amperage
Rating
Volts
(Vac)
Phase
3 KW Unit
15 KW Unit
Three
Phase
4.1 (9)
9 KW Unit
Nominal
Amperage Rating
Phase
12 (27)
Steam
Output
kg/hr
(lb/hr)
Steam
Output
kg/hr
(lb/hr)
20 (45)
25 (54)
41 (90)
Steam
Output
kg/hr
(lb/hr)
18 KW Unit
30 KW Unit
Three
Phase
Three
Phase
Steam
Output
kg/hr
(lb/hr)
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
208
84
41 (90)
—
—
—
—
—
—
125
61 (135)
240
—
—
—
—
96
54 (120)
—
—
—
—
400
—
—
51
45 (100)
—
—
73
—
—
480
—
—
—
—
—
—
58
—
—
600
—
—
—
—
—
—
47
—
—
65 (144)
Table 7-3. Steam Capacities and Rating Amperages
Volts (VAC)
HC6500/6500DI
30 KW Unit
33.5 KW Unit
40 KW Unit
48 KW Unit
45 KW Unit
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
240/220
—
—
144
82 (180)
—
—
—
—
400/380
77
30 (68)
—
—
110
145
480
—
—
—
—
87
116
600
—
—
—
—
70
93
98 (216)
130 (288)
Table 7-4. Steam Capacities and Rating Amperages
Volts
(Vac)
HC6500/HC6500DI
HC6700/HC6700DI
50.3 KW Unit
60 KW Unit
72 KW Unit
96 KW Unit
Air Gap
1” I.D. Clear Hose
Supplied with Unit
Fit Hose Inside
1-1/2” Pipe
1” or Larger
Copper Pipe
Figure 7-1 HC-6100/6300/6500/6700
Table 7-1. Recommended Branch Circuits
Table 7-2. Steam Capacities and Rating Amperages
Table 7-3. Steam Capacities and Rating Amperages
Table 7-4. Steam Capacities and Rating Amperages
Summary of Contents for HumidiClean HC-6100 Series
Page 28: ...HC6100 Wye Wiring layout 28...
Page 29: ...HC6100 Delta Wiring layout 29...
Page 30: ...30 HC6100 PAR Single Phase Wiring Layout...
Page 31: ...HC6300 Wye Wiring layout 31...
Page 32: ...HC6300 Delta Wiring layout 32...
Page 33: ...HC6500 Wye Wiring layout 33...
Page 34: ...HC6500 Delta Wiring layout 34...
Page 35: ...35 HC6500 WYE 2 contactors Wiring Layout...
Page 36: ...36 HC6500 Delta 2 contactors Wiring Layout...
Page 37: ...HC6700 Wye Wiring layout 37...