7
Repair Parts
SH-2000:
does not have repair part. If the trap fails, a new one will need to be installed
SH-2500:
does not have repair part. If the trap fails, a new one will need to be installed
AB-3000
• Remove the steam trap from the connector block by taking the two bolts out
• Unscrew and lift the cap
• Unscrew and replace the bimetallic element
• The distance between the flat bimetallic element and the seat should be 2 mm
• Clean or replace the screen
• Put the cap back on the body and screw the cap
• Bolt the trap back to the connector block