- 100 -
¾
Lock:
indicates that the UPS is locked, a lock is normally preceded by an alarm signal and, due to their gravity,
causes the inverter to be turned off and the load to be powered via the bypass line (this procedure is excluded
for locks caused by serious and persistent overloads and for a lock caused by a short circuit).
CODE
DESCRIPTION
L01
Incorrect auxiliary power supply
L02
One or more internal cables disconnected
L03
Phase 1 input fuse broken or input relay locked (will not close)
L04
Phase 2 input fuse broken or input relay locked (will not close)
L05
Phase 3 input fuse broken or input relay locked (will not close)
L06
BOOST stage overvoltage positive
L07
BOOST stage overvoltage negative
L08
BOOST stage undervoltage positive
L09
BOOST stage undervoltage negative
L10
Static bypass switch fault
L11
output undervoltage
L14
inverter overvoltage
L17
inverter undervoltage
L20
Direct voltage at output of inverter or Sine wave inverter distorted
L23
Overload at output
L26
Short circuit at output of Phase1
L29
output fuse broken or output relay locked (will not close)
L34
Heat sink 1 overtemperature
L35
Heat sink 2 overtemperature
L36
Heat sink 3 overtemperature
L37
Battery charger overtermperature
L38
Temperature probe of heat sink 1 faulty
L39
Temperature probe of heat sink 2 faulty
L40
Temperature probe of heat sink 3 faulty
L41
Temperature probe of battery charger faulty
L42
BOOST battery 1 fuse blown
L43
BOOST battery 2 fuse blown
L44
BOOST battery 3 fuse blown