- 102 -
UPS Models
10 kVA
12 kVA
15 kVA
20 kVA
Dimensions and weight
Width x Depth x Height
320 x 840 x 930 mm
Type of metal frame
Tower enclosure with wheels for transit, display inset in upper front section. Door
in lower front section giving access to switches and connections
Weight (without batteries)
80Kg
82Kg
90Kg
95Kg
Weight with batteries
180Kg
182Kg
190Kg
195Kg
Operation and efficiency
Operating Mode
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency)
Frequency Converter
AC/AC performance in on line mode
≥
93.5%
≥
94%
AC/AC performance in Eco mode
≥
98%
DC/AC performance in backup mode
≥
92.5%
≥
93.5%
Other features
Noise
≤
48dB(A)
≤
52dB(A)
Colour
RAL 7016
Environmental temperature
(7)
0 – 40 °C
Security Compliance
EN 62040-1-1, 2006/95/EC 73/23/EEC and 93/68/EEC directives
EMC Compliance
EN 62040-2 cat. C2. 2004/108/EEC, 93/68/EEC and 89/336/EEC directives
Battery Box Models
ET06P480A5-
(6)
ET06V480A0-
(6)
ET06P480M5-
(6)
ET06V480M0-
(6)
Battery
Nominal voltage per branch
240Vdc
Number of batteries/ V
40 / 12
80 / 12
Various
Environmental temperature
(7)
0 – 40 °C
Humidity
<95% non condensing
Protections
Over current – Short circuit
Safety Compliance
EN 62040-1-1, 73/23/EEC and 93/68/EEC directives
EMC Compliance
EN 62040-2 cl. C2 - 2004/108/EEC, 93/68/EEC and 89/336/EEC directives
Width x Depth x Height
320 x 840 x 930 mm
Weight
150 Kg
270 Kg
(1)
To keep the output voltage within the indicated precision range, retuning may be necessary following a long period of use
(2)
If the mains frequency falls within ± 5% of the selected value, the UPS is synchronised with the mains. If the frequency is outside
the tolerance range or operating off the batteries, the frequency will be the se0.1%
(3)
Mains/Battery @ 0% -100% load
(4)
@ Mains/ battery/mains @ 0% / 100% / 0% resistive load
(5)
The recharge current is adjusted automatically depending on the capacity of the battery installed.
(6)
The symbol “-” replaces an alphanumeric code for internal use
(7)
20 – 25 °C for longer battery life
(8)
@ 100% load & THDv
≤
1%