page 30 / 75 0MNA080A55-GB REV 01
3.6 Personalizations
Using the CONTROLS PANEL (from the basic menu press keys 3 and 5 and the access code 436215), the
following factory-set electrical parameters can be modified within a certain field:
-
Language (see page 55 ),
-
value of the RATED VOLTAGE OUTPUT (see page
59
) ,
-
BATTERY parameters (see page 59 ) ,
-
end of battery discharge pre-alarm (see page 60 ),
-
shutdown due to power lower than a set value (AUTO-OFF in power) (see page 62 ),
-
daily programmed shutdown (AUTO OFF time) (see page 62 ),
-
acceptance frequency and voltage field on the BY-PASS line (see page 63 ),
-
by-pass frequency field (see page 63 ),
-
modem configuration (see page 63 ),
-
RS232-1 and RS232-2 ports (see page 64 ).
-
standby-on operation (see page 28 ),
-
Smart active operation (see page 65),
-
date and time (see page
67
).
3.7
Procedure to transfer the load from UPS onto maintenance by-pass.
Procedure not applicable in the frequency converter
With several SENTRY MPS-HPs connected in parallel, follow the procedure described in the section on
“bypass for maintenance” of chapter “Parallel version”.
The sequences of operations to be carried out to place the UPS in maintenance bypass are shown below. The
procedure varies depending on the initial state of the UPS.
- SENTRY MPS-HP in NORMAL OPERATION
procedure a)
the power supply to the load is not interrupted in any way
;
- SENTRY MPS-HP with output not synchronized with the by-pass line
procedure b)
the power supply to the load is interrupted
(therefore this operation should be effected only if absolutely necessary).
Procedure a)
the by-pass line is present and its frequency and voltage are suitable
the UPS display panel
indicates
NORMAL OPERATION.
1)
close disconnecting switch SWMB (the control logic automatically disables the inverter)
2)
open all the switches on the device (SWIN, SWOUT, SWBY and the battery cabinet
disconnectors/fuses) and keep only disconnecting switch SWMB (maintenance by-pass line)
closed. The control panel remains off.
N.B.: After carrying out the operations indicated above, personnel must wait around ten minutes for the
capacitors to discharge before working on the inside of the UPS.
In this situation (during maintenance operations), any disturbance (such as a blackout) on the UPS supply
line would have an effect on the equipment powered (since the batteries are deactivated in this state).