page 54 / 75 0MNA080A55-GB REV 01
5.4
Control panel menu
5.4.1 Basic menu
If no commands have been inserted, the first line of the basic menu shows:
“NORMAL OPERATION”
if there are no alarms;
“ xxxxxxxxxxxxxxxxxxxxxxxxx ”
if there are alarms, the active ALARM messages are displayed one at a
time for a few seconds.
In each operating condition, the display returns to the "basic menu" after two minutes from the last
command inserted with the keys. The basic menu shows the signal messages relating to the current
operating state.
The second line of the basic menu shows:
The message OUT changes to BY when the load is not powered from the inverter (normal operation) but from the
mains through the by-pass line.
The message OUT=100%VA changes to OUT= SWMB when the load is powered through the maintenance by-pass
disconnector line, and the output current cannot be provided.
The value 100%VA provided in the example is obtained from the measurement of the output current.
The number indicates the output current with the value relating to the absolute rated value and the value indicated
is the greater of the effective current and the peak current.
- BATT= 100%Ah
: example of the current state of the percentage of battery recharge.
NORMAL OPERATION
_200 OUT=100%VA, BATT= 100%Ah, 5=ON
NORMAL OPERATION
_200 OUT=100%VA, BATT= 100%Ah, 5=ON
Model UPS
Power percentage absorbed by the load in output
State of battery charge
Acoustic alarm enabled/disabled
Rated power in kVA