page 72 / 75 0MNA080A55-GB REV 01
Electrical Data
SENTRY MPS-HP Power (kVA)
100
120
160
200
250
INVERTER
Rated power Pf 0.8 (kVA)
100
120
160
200
250
Active power Pf 1 (kW)
80 96 128 160 200
Active power with load power factor from
0.8 inductive to 0.9 capacitive (kW).
80
96
128
160
200
Rated power reduction factor (kVA/kW)
for cosfi =0.8 in advance
0.85
Rated voltage
400Vca 3-phase + N (configurable from 380V
to 415V)
Rated frequency
50 or 60Hz (configurable)
Rated voltage adjustment field
from 360 to 420V
Static variation
± 1%
Dynamic variation
± 5%
Recovery time within ± 1%
20ms
Conforms to standard EN 62040-3, class 1
Current peak factor (Ipeak/Irms as per EN
62040-3)
3:1
Voltage distortion with linear load
1% (typical), 2% (max)
Voltage distortion with non linear load (EN
62040-3)
< 3%
Stability of frequency with Inverter
synchronized with the by-pass mains
± 2% (adjustable from ± 1% to ± 6% from
control panel)
Stability of frequency with Inverter not
synchronized with the by-pass mains
± 0.05%
Speed of frequency variation
1Hz/sec
Dissymmetry of the phase voltages with
balanced and unbalanced load
≤
1%
Voltage phase shift with balanced and
unbalanced load
120 ± 1 °el
Overload with reference to the rated
power: Three-phase
110% for 60’ , 125% for 10’ , 150% for 1’
Single phase
200% for 7s
Shortcircuit current
Phase / Phase
180% for 1 second with current limiting
Phase / Neutral
300% for 1 second with current limiting
Inverter efficiency (%)
94%