4BHR5000 IMPLEMENTATION
0BHARRIS 5000 PROTOCOL
6.4.2.6. CONTROL OPERATE
Operates on a previously selected point. If the timeout has been reached between
selection and operation that is if more than 1 second elapses between the order of
selection and the order of operation, it will not run and will not respond anything to the
master.
Only complementary controls are accepted, and therefore only “Close” commands
are accepted on configured points. If in local or blocked mode, then there is no
answer.
If the message does not match with expected or if a point has not been previously
selected, it will not act and is not responding to the master.
6.4.2.7. POWER FAIL RESET
This function turns off the bit of “Power Fail” that the smART P500 activates when
starting the operation. In the smART P500 this flag is common to all ports.
6.4.2.8. PORT STATUS SCAN
All ports in HR5000 have 3 status bits which reflect the status of each port. With this
function the status of all the configured ports is requested. These 3 bits are:
OL: Off Line. Port out of service.
PF: Power Fail. Port reset.
MF: Failure of internal transfer of the port.
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...