2BINTEROPERABILITY
0BPROTOCOL IEC 60870-101/104
X
<10> := Measured value, normalized value with time tag
M_ME_TA_1
X
<11> := Measured value, scaled value
M_ME_NB_1
X
<12> := Measured value, scaled value with time tag
M_ME_TB_1
<13> := Measured value, short floating point value
M_ME_NC_1
<14> := Measured value, short floating point value with time tag
M_ME_TC_1
X
<15> := Integrated totals
M_IT_NA_1
X
<16> := Integrated totals with time tag
M_IT_TA_1
<17> := Event of protection equipment with time tag
M_EP_TA_1
<18> := Packed start events of protection equipment with time tag
M_EP_TB_1
<19>:= Packed output circuit information of protection equipment with time tag
M_EP_TC_1
<20> := Packed single-point information with status change detection
M_PS_NA_1
<21> := Measured value, normalized value without quality descriptor
M_ME_ND_1
X
<30> := Single-point information with time tag CP56Time2a
M_SP_TB_1
X
<31> := Double-point information with time tag CP56Time2a
M_DP_TB_1
<32> := Step position inform ation with tim e tag CP56Time2a
M_ST_TB_1
<33> := Bitstring of 32 bit with time tag CP56Time2a
M_BO_TB_1
X
<34> := Measured value, normalized value with time tag CP56Time2a
M_ME_TD_1
X
<35> := Measured value, scaled value with time tag CP56Time2a
M_ME_TE_1
<36> := Measured value, short floating point value with time tag CP56Time2a
M_ME_TF_1
X
<37> := Integrated totals with time tag CP56Time2a
M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Tim e2a
M_EP_TD_1
<39> := Packed start events of protection equipm ent with tim e tag CP56Time2a
M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag
CP56Time2a
M_EP_TF _1
Process information in control direction
X
<45> := Single command
C_SC_NA_1
X
<46> := Double command
C_DC_NA_1
<47> := Regulating step command
C_RC_NA_1
<48> := Set point command, normalized value
C_SE_NA_1
<49> := Set point command, sc aled value
C_SE_NB_1
<50> := Set point comm and, short floating point value
C_SE_NC_1
<51> := Bitstring of 32 bit
C_BO_NA_1
System information in monitor direction
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...