2.1.12.3. FREQUENCY DERIVATIVE (81R)
2.1.12.3.1. GENERAL DESCRIPTION
Each step activates the protection if the frequency derivative in Hertz per second
is higher than the programmed value. This function is effective only for frequencies
lower than a “maximum supervisory frequency” threshold and for currents above a
“minimum supervisory current” threshold. Figure 2-29 shows the logical diagram
for the frequency derivative function 81R