Doc.-no.: DPC200-MOD_02_EN
Issue: 08/2019
12
OPERATION
5.6 Adjustable parameters
Parameter
Selection or parameter range
default
Modbus
ON or OFF
ON
Modbus
address
1...247
1
Modbus
baudrate
7200, 9600, 14400, 19200, 38400, 57600
19200
Modbus
parity
none, even, odd, none_2_stop_bits
none
Unit
Pa and m³/h or InH
2
0 and cfm
Pa and m³/h
Operating
mode
Measuring mode or control mode
measuring
mode
Parameter
Differential pressure ΔP [Pa] or [InH
2
O]
Volume flow V [m
3
/h or cfm]
differential
pressure ΔP
[Pa]
Chracteristic
curve linear or square root
linear
K-factor:
Volume flow calculation according to: V = k · √Δp
with:
V = Volume flow in [m
3
/h] or [cfm]
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in [Pa] or [InH
2
O]
volume flow display indication up to 999,999
[m
3
/h or cfm] in
measuring mode and control mode
K = 70
Setpoint
differential pressure from 0 % p to 100 % of measuring range
Set = 8888
volume flow from 0,5 % up to 100 % of measuiring range,
k-factor is considered
Set = 8888
Output
voltage
0…10.0 V dc
U
out
= 10 V dc
P-gain
0...1,000
P = 50
I-gain
0…100.00
I = 3.15
Control
characteristic
positive/(heating):
Control deviation = set value – actual value
The output increases when: Set value > actual value
negative/(cooling):
Control deviation = actual value – set value
The output increases when: Actual value > set value
positive /
heating
If selected parameter = volume flow
than follows the additional input for the k-factor
fan k-factor
k = 70
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
OPERATION