13
Doc.-no.: DPC310_01_EN Issue: 01/2018
OPERATION
5.2 Adjustable parameters
Parameter
Selection or parameter range
Default setting
Unit
Pa and m³/h or InH20 and cfm
Pa and m³/h
Measuring
range:
DPC310-200 (Part-no: 2542)
0...200 Pa, 0...150 Pa, 0...100 Pa, 0...50 Pa
DPC310-1000 (Part-no: 2543)
0...1000 Pa, 0...750 Pa, 0...500 Pa, 0...250 Pa
DPC310-6000 (Part-no: 2544)
0...6000 Pa, 0...4000 Pa, 0...3000 Pa, 0...200 Pa
0...200 Pa
0...1000 Pa
0...6000 Pa
Operating
mode:
Measuring mode or control mode
measuring mode
Parameter
Differential pressure ΔP [Pa or InH2O]
Volume flow V [m
3
/h or cfm]
differential
pressure ΔP [Pa]
Characteristic
Characteristic curve linear or square root
linear
K-factor:
Volume flow calculation according to: V = k · √Δp
with: V = Volume flow in m
3
/h or cfm
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in Pa or InH20
volume flow display indication up to 999999 [m³/h or cfm]
in measuring mode or control mode
K = 70
Limit switch:
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 2 % up to 100 % of measuring range, k-factor is
considered.
OFF
Alarm delay
time:
switching delay time adjustment range:
1...60 seconds or 2....15 minutes
10 s
Switching
logic:
switching logic MIN or MAX
MAX
Contact logic:
contact logic active high or active low
active high
Setpoints:
differential pressure from 0 % up to 100 % of measuring range
volume flow from 2 % up to 100 % of measuring range, k-factor is
considered
Set 1 = 8888
Set 2 = 8888
Set 1 = 8888
Set 2 = 8888
Output
voltage:
0…10.0 V DC
U
out
= 10.0 V DC
P-gain:
0...1000
P = 50
I-gain:
0…100.00
I = 3.15
Control
characteristic:
positive/(heating): Control deviation = set value – actual value
The output increases when set value > actual value
negative/(cooling): Control deviation = actual value – set value
The output increases when actual value > set value
positive / heating
input function
•
OFF
- no function of 0...10 Vdc input
•
extern setpoint
- 0...10 V dc input is converted into setpoint
1 according to set measuring range and setting of parameter
(ΔP/V) and k-factor
•
temp ctrl setp
- 0...10 V dc input is converted into tempera-
ture (-30.0...+70.0°C) for setpoint compensation
OFF