18
Doc.-no.: DPC310_01_EN Issue: 01/2018
OPERATION
Start value of compensation
End value of compensation
Temperature reading
Result of compensation, is used for current control
Set value in menu for setpoint 1 / 2
Set value in menu for ‘compensated setp’
with:
t
2
=
t
1
=
t
mess
=
setpoint
comp
=
setpoint =
compensated setpoint =
5.6 Measuring range selection
The devices of the DPC310 series have each four adjustable measuring ranges, and are
available in three measuring groups.
Four preset measuring ranges in one device can be switched over in the menu.
To achieve this, the device must be located in menu at menu item ‚measuring range‘. The
measuring ranges can be switched with key T1. The displayed value is then used and stored
in the EEPROM. All other entries now refer to this value.
Differential pressure controller DPC310-200:
Measuring range
1: 0 ... 200 Pa
or
0 ... 0,8 InH2O
Measuring range
2: 0 ... 150 Pa
or
0 ... 0,6 InH2O
Measuring range
3: 0 ... 100 Pa
or
0 ... 0,4 InH2O
Measuring range
4: 0 ... 50 Pa
or
0 ... 0,2 InH2O
Differential pressure controller DPC310-1000:
Measuring range
1: 0 ... 1000 Pa
or
0 ... 4.0 InH2O
Measuring range
2: 0 ... 750 Pa
or
0 ... 3.0 InH2O
Measuring range
3: 0 ... 500 Pa
or
0 ... 2.0 InH2O
Measuring range
4: 0 ... 250 Pa
or
0 ... 1.0 InH2O
Differential pressure controller DPC310-6000:
Measuring range
1: 0 ... 6000 Pa
or
0 ... 24.0 InH2O
Measuring range
2: 0 ... 4000 Pa
or
0 ... 16.0 InH2O
Measuring range
3: 0 ... 3000 Pa
or
0 ... 12.0 InH2O
Measuring range
4: 0 ... 2000 Pa
or
0 ... 8.0 InH2O