background image

 

Doc.-no.:

 DS85P_01_EN   

issue: 

 09/2018 

 

6.  Error limits 

 

Zero 

deviation 

Final value 

deviation 

Linearity 

deviation 

Resolution 

hysteresis 

DS85P-200 

0…200 Pa 

± 0.5 % 

± 0.5 % 

± 0.25 % 

0.1 % 

1 % 

0…150 Pa 

± 0.75 % 

± 0.6 % 

± 0.4 % 

0.2 % 

0.7 % 

0…100 Pa 

± 1 % 

± 0.7 % 

± 0.5 % 

0.2 % 

0.5 % 

0…50 Pa 

± 2 % 

± 1 % 

± 1 % 

0.3 % 

0.5 % 

DE85P-1000 

0…1000 Pa 

± 0.5 % 

± 0.5 % 

± 0.25 % 

0.1 % 

0.2 % 

0…500 Pa 

± 0.7 % 

± 0.7 % 

± 0.5 % 

0.2 % 

0.2 % 

0…300 Pa 

± 0,9 % 

± 0.9 % 

± 0.9 % 

0.3 % 

0.2 % 

0…200 Pa 

± 1 % 

± 1 % 

± 1.25 % 

0.3 % 

0.2 % 

DS85P-6000 

0…6000 Pa 

± 0.5 % 

± 0.5 % 

± 0.25 % 

0.1 % 

0.2 % 

0…4000 Pa 

± 0.7 % 

± 0.7 % 

± 0.4 % 

0.15 % 

0.2 % 

0…3000 Pa 

± 0.9 % 

± 0.9 % 

± 0.6 % 

0.2 % 

0.2 % 

0…2000 Pa 

± 1 % 

± 1 % 

± 0.75 % 

0.25 % 

0.2 % 

Temperature drift (related to the respective highest measuring span) 

Zero point: 

± 0.2 % / K 

 

 

 

 

End value: 

± 0.3 % / K 

 

 

 

 

7.  Maintance 

The DS85P contains no wearing parts or consumables. Maintenance is not necessary. 
Upon request, Arthur Grillo GmbH offers an annual calibration with works certificate. In-
formation on this can be obtained from:  
 

Arthur Grillo GmbH

 

Am Sandbach 7 
40878 Ratingen 

Phone: 0 21 02 - 47 10 22 
Fax: 0 21 02 - 47 58 82 
E-Mail: info@grillo-messgeraete.de 

8.  Warranty 

Warranty and liability claims for personal property damage are excluded if they are at-
tributable to one or more of the following causes:  

 

Unapproved use of the device. 

 

Improper installation, start-up, operation and maintenance of the device.  

 

Unauthorized structural changes to the device beyond the intended purpose.  

 

Improperly carried out repairs.  

 

Disasters caused by foreign bodies and force majeure. 

Summary of Contents for DS85P

Page 1: ...Doc no DS85P_01_EN issue 09 2018 Installation and operation manual DS85P DIFFERENTIAL PRESSURE SENSOR Low pressure sensor with analogue output and selectable measuring ranges ...

Page 2: ... sensor store de Issue 09 2018 Doc No DS85P_01_DE This documentation including all parts is protected by copyright Any utilization or modi fication other than permissible under the strict limitations of copyright law is prohibited and liable to prosecution without the approval of the Arthur Grillo GmbH This applies in particular to duplications translations microfilming and storage and processing ...

Page 3: ...ls used 5 1 3 General notes 5 2 Product description 6 2 1 Intended use 6 2 2 Functional description 6 3 Montage 6 3 1 Dimension 7 3 2 Wall mounting 7 4 Start up 7 4 1 Pressure connections 7 4 2 Electrical connection 7 5 Measuring range selection 8 6 Error limits 9 7 Maintance 9 8 Warranty 9 9 Disposal 10 10 Technical specifications 10 10 1 CE label 11 ...

Page 4: ...al word for an important information about the product which should be drawn special attention to Hazard word Type of hazard Hazard source Hazard prevention 1 2 Pictograms and symbols used The following characters are used in this manual General danger symbol dan ger warning caution General information 1 3 General notes NOTICE These operating instructions contain instructions for the correct in st...

Page 5: ...fine tuned to each measuring range The deflection of the diaphragm is meas ured contactless with a differential transformer and converted into a standardized output signal by the electronics The ranges from 0 50 Pa to 0 6000 Pa are covered by three measuring range groups and in each device group four calibrated measuring ranges can be selected via a 2 pole DIP switch 3 Montage The differential pre...

Page 6: ...crews through the screw channels of the housing screws so that the screws protrude from the rear of the housing 5 Place the housing with the screws exactly on the fixing holes with the dowels 6 Tighten the screws 4 Start up 4 1 Pressure connections Connect all pressure connections properly with plastic hoses inner diameter 5mm 4 2 Electrical connection The differential pressure sensors are electri...

Page 7: ...ted via a 2 pole DIP switch under the rubber plug in the front cover Device typ DS85P 200 DE85P 1000 DS85P 6000 Measuring DIP switch range 1 2 MB1 off off 0 200 Pa 0 1000 Pa 0 6000 Pa MB2 on off 0 150 Pa 0 500 Pa 0 4000 Pa MB3 off on 0 100 Pa 0 300 Pa 0 3000 Pa MB4 on on 0 50 Pa 0 200 Pa 0 2000 Pa ...

Page 8: ...point 0 2 K End value 0 3 K 7 Maintance The DS85P contains no wearing parts or consumables Maintenance is not necessary Upon request Arthur Grillo GmbH offers an annual calibration with works certificate In formation on this can be obtained from Arthur Grillo GmbH Am Sandbach 7 40878 Ratingen Phone 0 21 02 47 10 22 Fax 0 21 02 47 58 82 E Mail info grillo messgeraete de 8 Warranty Warranty and liab...

Page 9: ...ift measuring span Due to 4 measuring ranges in 3 measuring groups TECHNICAL SPECIFICATIONS Operating mode measurement mode Medium Air or non aggressive gases Measuring sensor Electromechanical diaphragm movement Measurement unit Pa Smallest measuring span 0 50 Pa 0 5 mbar Largest measuring span 0 6000 Pa 60 mbar Measuring ranges 0 50 Pa 0 5 mbar 0 200 Pa 2 mbar 0 500 Pa 5 mbar 0 1000 Pa 10 mbar 0...

Page 10: ... label As electrical equipment the DS85P falls within the scope of the 2004 108 EC Directive EMC Directive The following standards have been applied within the scope of the EMC Directive DIN EN 61000 6 2 2006 03 corrigendum 1 2011 06 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environ ments DIN EN 61000 6 3 2011 09 Electromagnetic compatibility EMC Part 6 3...