500-003111-000
5-7
5.4.3
Analog Input Voltage Range Selection
As indicated in the Electrical Specifications (see Document Number
800-003111-000), five voltage ranges are available for the VMIVME-3111 Board.
Jumpers J3, J4, J6, and J15 control the ranges and are identified in Table 5.4.3-1.
The board is factory configured for ±10 V range.
Table 5.4.3-1. Voltage Range Configuration
J3 J4 J6 J15
±10
V
OFF 1,2 OFF 1,2
±5
V* OFF 1,2 OFF 2,3
±2.5
V ON 1,2 OFF 2,3
0 TO +5 V
ON
2,3
ON
2,3
0 TO +10 V**
OFF
2,3
ON
2,3
M3111/T5.4.3-1
*±5 V will also work with J3 ON, J4-1, 2, J6 OFF and J15-1, 2.
**0 to +10 V will also work with J3 ON, J4-2, 3, J6 ON and J15-1, 2.
Jumper J1 connects the P3 analog input return line to analog ground on
the VMIVME-3111 board. P3 input remote ground sensing is disabled if jumper J2 is
installed, and enabled if J2 is removed.
5.4.4
Current Loop Termination Resistors
The low pass input filter capacitors are replaced with 250
Ω
, 0.02 percent
precision resistors when the board is equipped with the current loop termination
option.
5.4.5 Differential/Single-Ended Input Mode Selection
All P3 analog inputs are single-ended channels. The P2 analog inputs,
however, can be jumper-programmed as either single-ended channels or as
differential channel pairs. A channel pair is differential if the associated jumper
(listed in Table 5.4-1) is removed. The pair becomes two independent
single-ended inputs if the jumper is installed.
5.4.6
Analog Output Voltage Range Selection
The analog output voltage range is selected by jumpers J12 and J13, as
indicated in Table 5.4-1. Jumper J39 connects the analog output return line to
analog ground on the VMIVME-3111 board.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com