background image

 

 

ISO 9001:2008 

  

   

 

                  OPTICAL SMOKE POINT DETECTOR 

          Model: 

SPD-3.10 

 

 

 

 

 

 

 

 

 

 

 

 

            USER’S  

            MANUAL 

 

 

              

Private enterprise "ARTON"

 

6  Prutska street

 

Chernivtsi 58008 Ukraine

  

 
                      

              

            EN 54-7

 

 
 

 
 
 
 
 
 
 
 
 
 
For further information please contact us: 
+38  0372 584373 

www.arton.com.ua

 

 

  

Summary of Contents for SPD-3.10

Page 1: ...2008 OPTICAL SMOKE POINT DETECTOR Model SPD 3 10 USER S MANUAL Private enterprise ARTON 6 Prutska street Chernivtsi 58008 Ukraine EN 54 7 For further information please contact us 38 0372 584373 www arton com ua ...

Page 2: ...and wiring can be found in Table 1 Table 1 Base Remote indicator Relay Relay contacts of the base Wiring B01 2 wire B1 2 wire B2 1 NC 4 wire B3 1 NO 4 wire B4 1 NC 4 wire B5 1 NO 4 wire B6 EOL 2 NO NC 4 wire B7 EOL 2 NO NO 4 wire B8 EOL 2 NO NC 4 wire B9 EOL 2 NO NO 4 wire Note denotes the presence of the function denotes its absence 2 TECHNICAL SPECIFICATIONS 2 1 Technical specifications of the S...

Page 3: ...ES OF OPERATION 4 1 The detector consists of the detector itself and the base The optical system the signal processing electronic unit and LED control circuit are in the plastic housing of the detector 4 2 For the appearance dimensions of the detector dimensions of the B01 base please refer to Figure 1 Figure 2 4 3 The principle of detector s operation is based on the control of optical medium den...

Page 4: ... detector s cover a plastic or metal pin Ø0 9 mm 40 50 mm long for at least 10 sec In not more than 10 sec the detector shall go to the alarm mode 5 2 9 Deenergize the detector The LED shall be on 6 LOCATION AND INSTALLATION 6 1 You should l detectors in places with the following conditions minimal vibrations of constructions minimal illumination intensity maximum distance from sources of electric...

Page 5: ...ortation and storage of detectors have been kept 8 3 In the case faults according to a reclamation have been removed the guarantee term is prolonged for the while detectors were not in use because of faults QUALITY AND PACKING CERTIFICATE Optical smoke detector model SPD 3 10 serial numbers _________________pieces With B01 base______________pieces With B__base_______________pieces Packed in compli...

Page 6: ...DIMENSIONS AND CONTACTS NUMERATION OF B01 BASE Figure3 WIRING DIAGRAM FOR SPD 3 10 WITH B01 TO DC CONTROL PANEL For 24 V CLR 0 36 2 kOhm EOL resistor from 2 4 to 10 kOhm depending on the control panel specifications For 12 V CLR 620 Ohm EOL resistor from 1 2 to 6 2 kOhm 1 2 7 8 ...

Page 7: ...EASE FALSE ALARM IMMUNITY EOL resistor and CLR correspond to Figure 1 Capacitors Сi ceramic 0 1 0 22 µF CEOL 22 µF 25 V Figure 5 WIRING DIAGRAM FOR SPD 3 10 WITH B01 TO AC CONTROL PANEL AL with current limited at 20 mA Diode VDEOL type 1N4148 EOL resistor 3 9 kOhm 0 25 W ...

Page 8: ...re 6 WIRING DIAGRAM FOR SPD 3 10 WITH B01 TO FIRE INTRUDER CONTROL PANEL THROUGH MUSH 1 MODULE MUSH 2 RN resistor 1 5 kOhm 0 25 W EOL resistor is specified by control panel specifications from 1 to 10 kOhm ...

Reviews: