22
1.
Inverter Output Voltage Adjustment
- When the inverter is running, connect an AC voltmeter to the inverter outputs (TP3, TP4 and TP5 on
ADVS01-R1 board).
- Keeping VR2, VR4, and V6 at approximately their mid-position, adjust the output voltages (roughly) to
their nominal value using VR7.
- Then re-adjust each phase voltage separately, again using VR2, VR4 and VR6 to their exact values
this time.
2.
DC Balance Adjustment
- When the inverter is running, connect a DC voltmeter to the inverter outputs (TP3, TP4 and TP5 on
ADVS01-R1 board)
- Adjust the DC voltage component of each phase of the inverter output to be ZERO, using VR1, VR3
and VR5.
3.
Inverter Output PLL Frequency Adjustment (for 50Hz nominal value)
- When the inverter is running, connect a frequencymeter to one of the inverter output phases (either
one of TP3, TP4 or TP5 on ADVS01-R1 board)
- Connect TP18 to TP12 (+12V) using a jumper wire and adjust the frequency to 51.4+/-0.1Hz using
VR8.
- Disconnect TP18 from TP12 and connect it to TP9(0V) this time (TP18-TP9) and check if the output
frequency is 48.6+/-0.1Hz.
- Repeat the adjustment procedure until you have equal frequency deviation around the center
frequency (50Hz)
- Let TP18 be NOT CONNECTED to anywhere and see that the inverter output frequency is equal to
the bypass supply (line voltage) frequency.
4.
Inverter Output Synchronization Adjustment
- Connect an AC voltmeter across the L3 phase of the inverter output (TP3 on the ADVS01-01 board)
and the L3 phase of the bypass input (TP6 on the ADVS01-01 board).
- Adjust VR9 to minimize the measured AC voltage across these points.
D)
P3MC Board Main Test Points
-TP3 : Triangle wave (9600Hz)
-TP5 : +5V supply voltage
-TP6 : +20V supply voltage
-TP8 : +6V supply voltage
-TP9 : 0V (GND)
-TP12 : +12V supply voltage
-TP18 : PLL analog signal (TP18 is connected either to +12V or to 0V during frequency adjustment)
-TP106 : L1 phase 50Hz square wave signal
-TP206 : L2 ‘’ ‘’ ‘’
-TP306 : L3 ‘’ ‘’ ‘’
-TP104 : L1 phase output feedback error signal
-TP204 : L2 ‘’ ‘’ ‘’ ‘’
-TP304 : L3 ‘’ ‘’ ‘’ ‘’
-TP107 : L1 phase reference sine-wave sample
-TP207 : L2 ‘’ ‘’ ‘’
-TP307 : L3 ‘’ ‘’ ‘’
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...