48
3.2.4 ADJUST Menu Items:
Only service personnel can use this menu ,the incorrect use of this menu can cause damage to the UPS.
Submenu item
Function
1 PASSWORD : XXX
Service password input
(-) key 100,
UP key 10,
(+) key 1 changes
after you write the password on screen press ENTER key ,if the
password is wrong the is no action.
If the password is okay a beep sounds and you see ADJUST
MODE at the second line.
2 ENTER <EXIT>
Enter
(
)
exit from submenu
Go to STATUS MENU
3.2.5 OPTIONS Menu Items
In this menu the user can set some important parameters for UPS operation..
Submenu item
Function
1 MODE: ONLINE
By using (+) and (-) keys you can move on 5 different operation modes.
ONLINE
: stand alone mode
PARALLEL
: 2 UPS in symmetric parallel operation
N+1 REDUNDANT
: 2 or more UPS in N+1 redundant parallel mode
REDUNDANT
: 2 UPS in redundant parallel mode.
ECONO:
Off-line mode.
press ENTER for 3 seconds and the selection is valid
2 UPS No : 001
By using PLUS and MINUS keys you can change number 0 to 3.
In parallel operation select different number for each UPS. If you select the
same number DUBL UPS NUMBER message tells the fault.
press ENTER for 3 seconds and the selection is valid
3 REMOTE :ENABLE
By using PLUS and MINUS keys you can change enable and disable
options.
enable
: remote battery test, shutdown and bypass functions are enabled
disable
: these functions are disabled
press ENTER for 3 seconds and the selection is valid
4 RESTART:ON/OFF
By using PLUS and MINUS keys you can change on and off options.
ON
: during mains failure, at the and of battery discharge UPS shutdowns,
and after mains is restored UPS starts again.
(battery trip out is on every time)
OFF
: after mains restoration UPS doesn’t start by itself again. (You must
turn off and then turn on the UPS)
(battery trip out is off)
press ENTER for 3 seconds and then the selection is valid
5
RELAY:BATT.LOW
/COMMON
By using (+) key the function of the RL3 Relay on the interface board can
be selected between Battery Low or Common Alarm.
6 BATTERY TEST:ON/OFF
By using PLUS and MINUS keys you can change on and off options. Used
to enable or disable automatic battery test.
7 ENTER <EXIT>
Enter
(
)
exit from submenu
Go to STATUS MENU
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...