50
3.2.7 TIME Menu Items
You can see date and time of RTC (real time clock) on UPS. And you can adjust date and time.
Submenu item
Function
1 TIME : 23 :15
time
2 DATE : 11-10-2006
date
3 SET HOURS: 11
(+) and (-) adjust hours (0-23)
4 SET MINS : 38
(+) and (-) adjust minutes (0-59)
5 SET DAY : 21
(+) and (-) adjust day (1-31)
6 SET MONTH : 06
(+) and (-) adjust month(1-12)
7 SET YEAR : 2006
(+) and (-) adjust year (2000-2099)
8 ENTER <UPDATE>
Enter update new date and time
9 ENTER <EXIT>
Enter
(
)
exit from submenu
Go to STATUS MENU
3.2.8 SERVICE Menu Items:
Submenu item
Function
1
HOURMTR: 00027
Total operation time of the UPS
2
MAX.LOAD:095%
Recorded max. load
3
TO B. TEST: 008Hr
Time until next automatic battery test.
4 ENTER <EXIT>
Enter
(
) Exit from submenu
Go to STATUS MENU
3.3 STATUS Messages
This message group simply shows the UPS STATUS on the upper line of LCD PANEL.
RECTIFIER START ! :
UPS started the rectifier
INVERTER START !
:
UPS started the inverter
MAINT SWITCH ON ! :
Maintenance bypass switch is on
MANUEL BYPASS !
:
Load is transferred to mains manually
STATUS ALARM !
:
Alarm status
STATUS NORMAL !
:
UPS is operating normally.
EMERGENCY STOP ! :
External emergency signal is detected.
WAITING SYNC !
:
Inverter started and waiting for synchronization
STATUS FAULT !
:
Fault status
STATUS WARNING ! :
Warning message is valid on LCD panel
CLOSE BATT.CB !
:
UPS is waiting for battery CB to be closed
INV. OUT FAILURE!
:
The UPS gave four successive “INV. BALANCE” error.
RECTIFIER START :
At start up the UPS controller board checks for input voltage, frequency, battery voltage for starting, if these
parameters are normal, it starts up.
INVERTER START :
If the inverter stops by any reason, controller board tries to restart the inverter. Each time the inverter is
started, this message appears on the first line of LCD PANEL
MAINT SWITCH ON:
Maintenance bypass switch is connected from bypass input to the output of UPS directly .If the
maintenance bypass switch is on (1 position) controller stops the inverter against any accidental short
circuits between mains voltage and inverter output. If the user turns off the maintenance bypass switch,
inverter starts again.
EMERGENCY STOP :
If an external EPO switch is installed to system (connected to interface board), it is possible to stop all UPS
parts (rectifier, static bypass, inverter, etc….). After pressing EPO switch, the rectifier and inverter are
turned off and the power to the critical load is turned off. To start again, turn off the ON/OFF switch and turn
it on again.
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...