53
ALARM
DESCRIPTION
A28
P.FAILURE 21
Parallel controller board failure
A29
P.TEST MODE
Parallel controller is in test mode
A30 P FAILURE 23
Parallel controller board failure
A31
DUBL UPS NR.
Same UPS number is used for two UPS in the parallel system.
Possible Causes:
1) Change number(s) in OPTIONS Menu.
A39 PSP FAILURE1
Control Power supply fault.
A40 CANT FIND PR
One of parallel modes is selected but there is no parallel control board on
UPS
Change mode from OPTIONS Menu.
A41 P.BAL.FAILURE
In parallel operation current sharing is not okay
A42 BATTERY TEST
Performing battery test
A43 P.SYNC.FAIL
In parallel system SLAVE UPS is not synchronized to MASTER UPS
A44 BT.OPERATION
UPS is operating on batteries
Possible Causes:
1) AC line voltage is not available or out of tolerated voltage limits.
2) Distribution problems or blown fuse(s)
A45 MAINS OK
After mains failure, mains voltage restored again. This message appears on
screen for 15 seconds after mains restoration.
A46 BOOST CH.END
Boost charging period has been completed, normal float charging conditions
are valid.
A47 CANNOT START
Inverter can not start because of an internal fault.
A52 MANUA. BYPASS
Load transferred to bypass supply from COMMAND MENU
A64 INV. BALANCE
DC balance problem at the Inverter output. Call service.
A65 MAINS HIGH
AC Input Voltage above the tolerated value
Additional Alarm codes for Parallel Operation (Optional).
ALARM
DESCRIPTION
P05 P.SYNC. ALARM
In parallel system SLAVE UPS is not synchronized to MASTER UPS
P07 P.BAL. ALARM
In parallel operation current sharing is not okay (temporary)
P10 P.CLK ALARM
There is an interruption or false status on parallel synchron signal between 2
UPS (temporary)
P16 MODE FAILURE
SLAVE ups search for the same operating mode with MASTER ups, if they
are different this message is seen on LCD panel.
Change the operation mode of SLAVE ups from OPTIONS MENU.
Don’t forget to press ENTER key for 3 seconds
Turn off the SLAVE ups and turn on again.
P17 RS485 ALARM
There is an interruption or false status in parallel communication between the
UPSs
P19 DATA CABLE
Data connection cable between parallel UPS is not OK (bad connection or
cable mismatch)
P20 ONLY ONLINE
There is an online UPS in parallel system, please change the operation mode
P21 PLUG IN DIG.
The digital connection cable between parallel UPSs is unplugged
P23 PSP FAILURE 2
Parallel controller board isolated power supply is out
P24 DUBL UPS NR.
Same UPS number is used in parallel system.
Change from OPTIONS MENU
P25 NO CLOCK
During power up the synchron clock signal is lost by slave UPS
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...