55
The AC inputs of all UPSs in the parallel system are connected to the same mains, and all the AC outputs
are connected to each other. Each UPS has its own battery group. The critical load is connected to the
common output of the parallel system. There are also some signal cable connections between the UPS
units necessary for parallel operation, and will be described later.
4.2 Parallel Operation Modes of ARTonPlus Series
UPSs
NOTE: Parallel operation hardware (parallel controller boards and some other accessories) are not
installed in a standard ARTonPlus Series UPS, but parallel operation option is available and can
easily be added to all UPSs.
Parallel operation is possible in one of the three modes:
1) PARALLEL operation (power increase)
2) REDUNDANT parallel operation
3) N+1 REDUNDANT parallel operation
NOTES:
1- The preferred mode for parallel operation can be selected using OPTIONS MENU.
2- For parallel operation, each UPS must be assigned a unique UPS No again using OPTIONS MENU.
4.2.1. PARALLEL mode
This mode should be selected for increasing the available UPS power capacity.
If this mode is selected
for parallel UPS operation, the total VA rating of the parallel system is the sum of the VA ratings of
all the UPSs connected in parallel.
The output load is equally shared by each UPS in the parallel system.
Mains power is used as the spare energy supply (BYPASS).
In case of a failure in one of the UPSs, the Static Bypass Switches of all UPSs are turned on
and the load is transferred totally to the spare energy supply (usually mains voltage) without any
interruption. If the fault is cleared and if everything returns to normal operating conditions, the Inverters of
all UPSs in the parallel system resume the load together at the same time.
The output load of the parallel system is shared equally by each UPS, both during Inverter or Bypass
operation.
If this mode is active, you will see ‘’PARALLEL MODE/MS’’ on the LCD panel of one of the UPSs, and you
will see ‘’PARALLEL MODE/SL’’ on the LCD panels of all the other UPSs connected in the parallel system
(MS meaning Master and SL meaning Slave).
In PARALLEL mode, the Static Bypass Switches of all the UPSs in the parallel system act (turns on or off)
simultaneously. During normal PARALLEL operation, the load is shared equally by the inverter outputs of
each UPS provided that the output switches of all UPS units are turned on. In case of a failure in one of the
UPS units or if the output switch of one of the units is turned off, the static bypass switches of all the
parallel units are turned on simultaneously and the critical load is transferred to the bypass supply without
any interruption.
In other words, during operation in PARALLEL mode, the parallel UPS system behaves like a single
(stand-alone) UPS with a higher power rating.
4.2.2. REDUNDANT mode
This mode is used for operation of two (or more) UPS units connected in parallel, for increased reliability. If
this mode is selected, the load is shared equally by each UPS available in the parallel system, during
normal operation.
In case of failure of one (or more) of the UPSs, the faulty UPS is isolated from the parallel system and the
critical load is still supplied by the remaining UPSs. If the faulty UPS returns to normal operation , it joins
the parallel system again and starts sharing the load.
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...