59
V. OPERATING INSTRUCTIONS
After completing the installation of the unit, and connecting all the power cables with all switches and fuses
in “OFF” position,
1.
Check the battery polarities.
K1 : + V (+360V Nominal, +405V under float charge)
K2 - K2 : 0 Volts (connected to the midpoint of the 60 blocks battery string)
K3 : - V (-360V Nominal, -405V under float charge)
2.
Check the 3 phase AC input and neutral connections. (Phase sequence is important)
NOTE THAT SEPARATE CABLES FROM EACH BATTERY GROUP SHOULD BE CONNECTED TO K2
TERMINALS TO FORM THE MIDPOINT CONNECTION!
WARNING!!! The UPS must never be turned on without input neutral connection.
3.
Check the output (load) connections.
5.2.1
Procedure For Turning On The UPS To Supply The Load From A Complete Power-
Off Condition
1.
Turn on S1 (AC Input)
2.
Turn on S2 (Bypass)
3.
Turn on S4 (AC Output)
ATTENTION!!! AS SOON AS YOU TURN ON ON/OFF SWITCH (S7), BYPASS VOLTAGE WILL
APPEAR ON THE OUTPUT TERMINALS.
4.
Turn on S7 (ON/OFF Switch), LCD panel will start running. “RECTIFIER START” message will appear
on the front panel.
5.
When “INVERTER START“appears on the front panel turn on S5 (Battery) into “1”
position.
After a few seconds, the BYPASS led L4 (red) will turn off and the INVERTER led L6 (green) will turn on.
The UPS is ready for uninterrupted operation when “STATUS NORMAL/ONLINE MODE” message
appears on the front panel.
5.2.2 Power Off
After turning off all the loads connected to UPS output:
1.
Turn off S4 (AC Output) into “0” position.
2.
Turn off S7 (ON/OFF Switch) into “0” position.
3.
Turn off S5 (Battery) into “0” position.
4.
Turn off S2 (Bypass) into “0” position.
5.
Turn off S1 (AC Input) into “0” position.
This is a complete power off condition and both RECTIFIER and INVERTER are not operating in this
case.
5.1 INTRODUCTION
5.2 OPERATING INSTRUCTIONS FOR A SINGLE UPS UNIT. (ONLINE OPERATION)
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...