66
In “RS232” position of DIP switches, RS232 communication with an external device is performed through
the standard DB9 socket shown above. If DIP switches are in “INTERNAL” position, communication through
the standard socket is turned off and routed to an internally connected device. For example, if an ML100
Port Multiplexer has been installed in the UPS, standard DB9 socket is not used for RS232 communication,
instead, the two ports, COM1 and COM2 on the ML100 can be used for external communication
simultaneously.
8.2 Serial Communication Cable
The maximum length for RS232 communication cable should be 25 meters. Cable connector pin
configuration is as follows:
UPS side
PC side
9 Tx
2 Rx
7 Gnd
5 Gnd
6 Rx
3 Tx
For remote panel and UPS connection the same pin configuration is valid.
8.3 Modem Connection
A ARTonPlus Series UPS can be controlled through a normal telephone line by means of a remote
operator connected through a PC with modem device, who performs a phone call to the UPS connected
number. So the operator can see all parameters and control the UPS (if permitted from OPTIONS MENU).
8.3.1 Hardware Configuration
All requirements for modem connection are as follows:
PC with modem
WINDOWS 98
Available UPS control software (T-MON)
NULL modem which is connected to UPS
In order to perform this function a PC with UPS control software and an external or internal modem device
connected to telephone line are needed.
A NULL modem device, configured according to NULL and auto answer modes, when installed in the UPS
and, once programmed, following a telephone call of the PC-embedded modem, will connect the UPS to
the telephone line.
8.3.2 Functioning Principle
The remote operator, by means of a PC and a modem device and using the remote connection function of
the control software, calls the UPS through the number to which this is connected.
The NULL modem device, connected to the UPS, will answer the call and convert the data coming from
UPS’s serial port on to the telephone line. This way all measurements and controls allowed by the RS232
serial port can be carried out.
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...