INVERTER
: It is manufactured by using the latest IGBT technology and Pulse width Modulation (PWM)
technique. The Inverter converts the DC BUS voltage supplied by the IGBT Rectifier and / or the batteries
into a well regulated 3-phase AC voltage with fixed voltage and frequency.
The output of the inverter is used to supply the critical loads connected to the UPS output.
STATIC TRANSFER SWITCH (STATIC BYPASS) :
This is an electronically controlled transfer switch,
which enables the critical load to be connected either to inverter output or to a by-pass power source.
During normal operation, the load is supplied by the inverter output, but in case of an overload it is
automatically transferred to the bypass source without any interruption.
MAINTENANCE BYPASS SWITCH (MBS) :
This is a manually controlled mechanical switch, which is
used to supply the critical load, using the bypass source, when the UPS is shut down for maintenance or
troubleshooting purposes.
The load is unprotected against mains supply disturbances and black-outs when it is connected to either
static or maintenance bypass supply.
1.2.1 OPERATING MODES OF UPS
ARTonPlus Series UPSs are capable of operating in various different modes for maximum application
flexibility. These modes are:
-
ONLINE mode:
This is the normal operation mode for a single UPS. As long as the mains supply is
available and in required tolerances, the load is supplied by the well regulated inverter output and the
batteries are charged at the same time. In case of mains failure, the inverter keeps supplying the load
using the energy stored in the batteries.
-
ECONO mode:
This is the off-line operation mode for a single UPS. As long as the mains supply is
available and in required tolerances, the load is supplied by the mains supply (bypass supply) via the
Static Bypass Switch of the UPS and the batteries are charged at the same time. During that time
inverter keeps running under no-load conditions and takes over the load in case of a mains supply
(bypass supply) failure, without any interruption. After restoration of the mains supply the load is
transferred back to bypass supply again.
- PARALLEL, REDUNDANT
and
N+1 REDUNDANT modes
are used for parallel operation of two or
more UPS units and will be explained in parallel operation section later in this manual.
When operating in one of the above operating modes, UPS may be in one of the following operating
conditions:
A. Normal Operation (If Mains supply is available):
All fuses and power switches are closed (except the Maintenance Bypass Switch), and the load is
supplied by the Inverter Output. During normal operation, the Rectifier supplies DC power to the Inverter
and charges the Batteries at the same time.
B. Battery Operation :
The Batteries are connected to the Rectifier output. In case of a mains failure (mains power outage or
AC input voltage out of tolerance), the Rectifier stops operating and the DC voltage necessary for the
inverter operation is supplied by the batteries. Therefore the AC voltage output supplying the critical
load is not interrupted, until the batteries are fully discharged. At the end of the discharging time the
Inverter is turned off and it start again automatically, together with the Rectifier, when the mains power
is restored, and the UPS returns o normal operation.
The Rectifier is also turned off and Inverter operates on batteries during automatic or manual battery
test procedure.
C. By-Pass Operation :
If the Inverter output is overloaded or in case of a problem in the UPS, the static switch transfers the
load to the bypass supply without any interruption, provided that the bypass supply is available and
within the tolerated limits.
At the end of the overloading period, if the fault condition is restored, static switch transfers the critical load
again to the inverter output. Note that, during operation from the bypass supply, the critical load may be
effected by any possible disturbances or power failure in the bypass supply.
Summary of Contents for ARTon Plus series
Page 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Page 2: ......
Page 13: ...9 Figure 1 4 2 IGBT Rectifier...
Page 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Page 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Page 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Page 23: ...19 Figure 1 5 4 IPMD3P Board...
Page 28: ...24 Figure 1 5 5 P3MC R5 Board...
Page 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Page 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Page 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Page 39: ...35 Figure 1 5 11 OPS3 Board...
Page 40: ...36...
Page 41: ...37...
Page 42: ...38...
Page 73: ......
Page 74: ...1 AGKK7080 01 2008...