Installation, Operation and Maintenance Manual

8221  RevD  08-18

7

V

WARNING

• 

Confirm XO N-G Bonding at Upstream Transformer

• 

Do Not Hi-Pot Test

• 

Resulting Damage is not Covered Under Warranty

VERIFY THAT ALL POWER CIRCUITS ARE DEENERGIZED 

BEFORE MAKING CONNECTIONS

All electrical connections should be performed by a qualified (licensed) 

electrician or technician. All wiring must comply with the National Electrical 

Code (NEC®) and applicable local codes.

V

WARNING

A

B

C

G

N

BREAKER

(Type 1 or individual equipment installations may vary)

 

Use closest breaker to SPD

 

Locate SPD close to intended 

breaker

 

Keep Leads Short as Possible

 

Avoid Sharp Bends

 

Rotate S50A such that LED  

indicator is most visible

 

Outdoor installation requires 

appropriate weather sealing at nipple 

(gasket, sealing conduit, etc.)

To Protected Loads

FIGURE 3: TYPICAL PANEL INSTALLATION

FIGURE 4: NIPPLE

Sealing Gasket:  

Two choices 

1.) At 3/4" nom. thread: ID is 1.05"

2.) At 0.14" high 'base step': ID is 1.25"

Summary of Contents for 400 Series

Page 1: ...Surge Protective Devices Installation Operation Manual S50A ...

Page 2: ...icos incluyendo DINP que es conocido por el Estado de California como causantes de cáncer y DIDP que es conocido por el Estado de California como causante de defectos de nacimiento u otros daños reproductivos Para mayor información visite www P65Warnings ca gov AVERTISSEMENT Ce produit peut vous exposer à des agents chimiques y compris DINP identifiés par l État de Californie comme pouvant causer ...

Page 3: ...Figure 4 Nipple Figure 5 Dimensions Weight Figure 6 S50A Mounting Options Voltage Rating Application SPDs on Ungrounded Systems Connecting Optional Form C Dry Contact Audible Alarm Figure 7 Leads 6 6 7 7 8 8 8 9 9 9 NORMAL OPERATION Green LED Indicator Form C Dry Contact and Audible Alarm Option Maintenance Troubleshooting Service 10 10 10 10 10 INTRODUCTION Figure 1 NEC Article 285 UL 1449 4 Part...

Page 4: ...R MUST SEAL THE CONDUIT NIPPLE USING WATERTIGHT FITTINGS NOT INCLUDED TO ENSURE A WATERTIGHT CONNECTION READ THIS MANUAL IN ITS ENTIRETY PRIOR TO INSTALLING In the late 2000 s there were significant nomenclature changes associated with a revision to UL 1449 and 2008 NEC Article 285 The S50A complies with latest regulatory actions and is UL 1449 CSA 22 2 No 269 listed as such VZCA E321351 There is ...

Page 5: ...luding leads See UL Label markings on SPD or see Data Sheet for specs Supplemental overcurrent protection is not required to protect this SPD However NEC and CEC convention requires that connecting conductors have overcurrent protection in Type 2 applications Follow applicable codes This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppres...

Page 6: ... See Data Sheet for specs and wire outs 2 Determine Mounting method See Figure 6 weather resistant equipment may be required 3 If SPD has optional Dry Contact pre plan its installation 4 Remove power from panel source Confirm panel source is de energized 5 Identify breaker location and SPD location Position SPD such that LED is best visible 6 Mount SPD weather resistant applications require additi...

Page 7: ...mply with the National Electrical Code NEC and applicable local codes V WARNING A B C G N BREAKER Type 1 or individual equipment installations may vary Use closest breaker to SPD Locate SPD close to intended breaker Keep Leads Short as Possible Avoid Sharp Bends Rotate S50A such that LED indicator is most visible Outdoor installation requires appropriate weather sealing at nipple gasket sealing co...

Page 8: ...ault conditions During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system FIGURE 5 DIMENSIONS WEIGHT 3 26 3 26 1 15 4 13 3 4 14 Sized for std 35mm DIN Rail 3 31...

Page 9: ...r failed wiring whereas Normally Open does not If the dry contacts are not utilized insulate lead ends coil and secure Audible Alarm will still function correctly The contact is rated 250V 5A Higher energy applications require supplemental relaying This option monitors suppression element condition and is not intended for use as phase loss or phase detection monitoring NORMAL OPERATION Green LED I...

Page 10: ...s also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend to be symptoms not root causes We suggest treating a failed SPD as a canary in the coal mine as there may be larger issues at play As a generalization the single largest killer of SPDs is reference to ground issues If the SPD shows problems on startup there is reasonable cha...

Page 11: ...Installation Operation and Maintenance Manual 8221 RevD 08 18 11 ...

Page 12: ...iterature ASCO assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2018 ASCO Power Technologies All Rights Reserved 14550 58th Street North Clearwater Florida 33760 P 800 727 0669 F 727 539 8955 W www surgeassure com ...

Reviews: