Installation
ASCO Model K875A Outdoor Load Bank
3-9
LOAD SHED CONTROLLER (Optional)
Wire the current transformer into the control circuitry as shown on the provided schematic.
*******************************************************
W A R N I N G
Always put a short or shunt across the current transformers when
servicing the Load Bank. Primary current flowing through an
unshunted current transformer will destroy the transformer with
possible harm to personnel.
*******************************************************
THEORY OF OPERATION
The automatic operation circuitry of the Load Bank allows the generator to maintain a minimum
percentage of its rated output for efficient generator operation. The control range is generally
between 60% and 80% of the output rating of the generator.