ASCO 4ATE, 4ACTE, 4ADTE, 4NTE, 4NCTE, 4NDTE
Installation Manual
Page 8
ASCO Power Technologies
381333-445 B
Bypassing & Isolating
continued
Bypassing the ATS
This procedure explains how to bypass the closed transfer switch contacts. Bypassing is required before the Transfer Switch can
be tested or isolated. The
Bypassed
lights must be off and the
Connected
light must be on. See Figure 4.
1.
Observe which
ATS On
light is on (Normal or Emergency). This is the position of the transfer switch.
2.
Follow below to bypass the same source as that which is connected to the transfer switch (select Normal or Emergency).
Bypass to the Normal Source
(When ATS is connected to Normal Source)
1.
Press and hold the
Bypass to Normal
button until the
Bypassed to Normal
light comes on.
Figure 5. Bypass to Normal button
Figure 6. Bypass to Normal diagram
Figure 7. Bypassed to Normal light
Bypass to the Emergency Source
(When ATS is connected to Emergency Source)
1.
Press and hold the
Bypass to Emergency
button until
the
Bypassed to Emergency
light comes on.
Figure 8. Bypass to Emergency button
Figure 9. Bypass to Emergency diagram
Figure 10. Bypassed to Emergency light
This green light will turn on.
This red light will turn on.
This light
must be on
indicating it is
permitted to
bypass
The Bypass
Switch closes
its normal
contacts.
The Bypass
Switch closes
its emergency
contacts
.
This light
must be on
indicating it is
permitted to
bypass