3--22 Initial Set up
Engine Run Time Counter and Reset
This screen is used only when the Emergency source is monitored by the Power
Manager Xp (see page 3–2). It records the total time of the running generator
(above 50 % of nominal emergency voltage) in minutes and hours (elapsed time).
The counter can be turned on or off by selecting
ENABLED
(on) or
DISABLED
(off) as shown below.
The counter is updated once a minute and the cumulative time is stored in non–vol-
atile memory (EEPROM) every 15 minutes. The counter can be reset to 0 as shown
below. After 65,535 hours it resets to 0 automatically.
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<< Engine Run Time >>
DISABLED
Time:
123456 h 59
Clear Counter ?
NO
Press left & right
arrow keys until
Engine Run Time
appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<< Engine Run Time >>
DISABLED
Time:
123456 h 59
Clear Counter ?
NO
The word
DISABLED
is blinking.
6
<< Engine Run Time >>
ENABLED
Time:
123456 h 59
Clear Counter ?
NO
Press up & down
arrow keys until
word ENABLED
appears.
7
<< Engine Run Time >>
ENABLED
Time:
123456 h 59
Clear Counter ?
NO
The word NO
is blinking.
8
<< Engine Run Time >>
ENABLED
Time:
123456 h 59
Clear Counter ?
YES
Press up & down
arrow keys until
the word YES
appears.
9
<< Engine Run Time >>
ENABLED
Time:
0 h 00
Clear Counter ?
NO
Resets the
counter to zero.
Nothing is
blinking.
Now press the
Esc
key to return to the top level display.