Ascon Tecnologic - e30V - OPERATING INSTRUCTIONS - PAG. 3

3.  USAGE WARNINGS

3.1 

Admitted use

D

D

The instrument has been projected and manufactured 
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.  

Using the instrument for applications not expressly permitted 
by the above mentioned rule must adopt all the necessary 
protective measures.
The instrument 

MUST NOT BE USED

 in dangerous environ-

ments (flammable or explosive) without adequate protections.
The instrument used with NTC 103AT11 probe (identifiable 
by the printed code “103AT-11” visible on the sensor part) 
is compliant with standard EN 13485 (“Thermometers for 
measuring the air and product temperature for the transport, 
storage and distribution of chilled, frozen, deep-frozen/quick-
frozen food and ice cream”) with the following classification: 
[EN13485 air, S, A, 2, -50°C +90°C]
Remember that the end user must periodically check and veri-
fy the thermometers in compliance with standard EN 13486.
The installer must ensure that the EMC rules are respected, 
also after the instrument installation, if necessary using 
proper filters.

4.  INSTALLATION WARNINGS

4.1 

Mechanical mounting

The instrument, in case 78 x 35 mm, is designed for flush-
in panel mounting.  Make a 71 x 29 mm hole and insert the 
instrument, fixing it with the provided special brackets.
We recommend that the gasket is mounted in order to obtain 
the front protection degree as declared.
Avoid placing the instrument in environments with very high 
humidity levels or dirt that may create condensation or intro-
duction of conductive substances into the instrument
Ensure adequate ventilation to the instrument and avoid 
installation in containers that house devices which may 
overheat or which may cause the instrument to function at a 
higher temperature than the one permitted and declared.
Connect the instrument as far away as possible from sources 
of electromagnetic disturbances such as motors, power re-
lays, relays, solenoid valves, etc..

4.2 

Dimensions [mm]

4.2.1 

Mechanical dimensions

P

U

e30V

28

12.2

14.5

8

6

34

78

35

4.2.2 

Panel cut-out

29 

+0.6

71 

+0.6

RECOMMENDED
PANEL CUTOUT

min.

 12 mm

min. 15 mm

4.2.3 

Mounting

Brackets

Panel + Gasket max. 2.5 mm

34

Summary of Contents for e30V

Page 1: ...scription The E30V model is a digital microprocessor electronic ther mometer with NTC input probes equipped with functions for temperature alarms The instrument is available with a keyboard or without...

Page 2: ...eter at this point i possible to program the instrument in the same way previously described The password protection can be disabled by setting tPP oF Normal mode 2 s 5 s Increase value Decrease value...

Page 3: ...er must ensure that the EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35...

Page 4: ...be used Furthermore the input cable of the probe has to be kept sepa rate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground at only one side 4 3...

Page 5: ...nt the A01 must be correctly supplied AC supply Supply adapter 12 VDC Enter PWS 12 V A B C TTL USB to PC USB For additional info please have a look at the A01 instruc tion manual 7 PROGRAMMABLE PARAME...

Page 6: ...andards in force on waste disposal 9 TECHNICAL DATA 9 1 Electrical characteristics Power supply 230 VAC 115 VAC 24 VAC VDC 12 VAC VDC 10 AC frequency 50 60 Hz Power consumption about 2 VA Inputs 1 inp...

Page 7: ...30 VAC C 115 VAC L 24 VAC VDC F 12 VAC VDC b NOT USED d DISPLAY I Red standard C Blue c TERMINALS V Screw terminals standard E Complete removable screw terminals N Removable screw terminals fixed part...

Page 8: ...Ascon Tecnologic e30V OPERATING INSTRUCTIONS PAG 8...

Reviews: