Ascon Tecnologic - e30V - OPERATING INSTRUCTIONS - PAG. 6

8.  PROBLEMS, MAINTENANCE AND WARRANTY

8.1 

Notifications

8.1.1 

Error messages

Error

Reason

Action 

E1 -E1

The probe may be interrupted 
(

E

) or in short circuit (

-E

) or 

may measure a value outside 
the range allowed

Check the probe connec-
tion with the instrument 
and check that the probe 
works correctly

epr

Internal EEPROM memory 
error

Press 

P

 key

err

Fatal memory error

Replace the instrument or 
ship to factory for repair

8.1.2 

Other messages

Message

Reason

Hi

Maximum temperature alarm in progress

Lo

Minimum temperature alarm in progress

8.2 

Cleaning

We recommend cleaning of the instrument only with a slightly 
wet cloth using water and not abrasive cleaners or solvents.

8.3 

Warranty and Repairs

The instrument is under warranty against manufacturing flaws 
or faulty material, that are found within 18 months from deliv-
ery date.  The warranty is limited to repairs or to the replace-
ment of the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period 
of warranty, or further to its expiry, please contact our sales 
department to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alternative 
agreements.

8.4 

Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

9.  TECHNICAL DATA

9.1 

Electrical characteristics

Power supply:

 230 VAC, 115 VAC, 24 VAC/VDC,  

12 VAC/VDC ±10%;

AC frequency:

 50/60 Hz;

Power consumption:

 about 2 VA;

Inputs:

 1 input for NTC temperature probes (103AT-2, 10 k

W

 

@ 25°C);

Overvoltage category:

 II;

Protection class:

 Class II;

Isolation:

 Reinforced insulation between the low voltage 

parts (type C or D power supply) and front panel; Reinforced 
insulation between the low voltage parts (type C or D power 
supply) and the extra low voltage section (inputs); No isolation 
between power supply (type F or L power supply) and input.

9.2 

Mechanical characteristics

Housing:

 Self-extinguishing plastic, UL 94 V0;

Ball Pressure Test as described in EN60730:

 accessible 

parts 75°C; support live parts 125°C;

Heat and fire resistance category:

 D;

Dimensions:

 78 x 35 mm, depth 34 mm;

Weight:

 About 90 g;

Mounting:

 Incorporated flush in panel (thickness max. 2.5 

mm) in a 71 x 29 mm hole;

Connections:

Inputs:

 Fixed or removable screw terminal block for  

0.14 ÷ 1.5 mm

2

/AWG 28 ÷ 16 cables;

Power supply:

 Fixed or removable screw terminal block 

for 0.2 ÷ 2.5 mm

2

/AWG 24 ÷ 14 cables;

Protection degree:

 IP65 mounted with gasket;

Pollution degree:

 2;

Operating temperature:

 0 ÷ 50°C;

Operating humidity:

 < 95 RH% with no condensation;

Storage temperature:

 -25 ÷ +60°C.

9.3 

Functional features

Measurement range:

 NTC: -50 ÷ +109°C/-58 ÷ +228°F;

Display resolution:

 1° or 0.1° (range -99.9 ÷ +99.9°);

Overall accuracy:

 ±(0.5% fs + 1 digit);

Sampling rate:

 130 ms;

Display: 

3 Digit Red (Blue optional), height 17.7 mm;

Software class and structure:

 Class A;

Compliance:

 Directive 2004/108/CE (EN55022: class B; 

EN61000-4-2: 8kV air, 4kV cont.; EN61000-4-3: 10V/m; 
EN61000-4-4: 2kV supply and relay outputs, 1kV inputs; 
EN61000-4-5: supply 2kV com. mode, 1 kV\diff. mode; 
EN61000-4-6: 3V),  
Directive 2006/95/CE (EN 60730-1, EN 60730-2-9), 
Control 37/2005/CE (EN13485 air, S, A, 2, -50°C +90°C with 
probe NTC 103AT11).

Summary of Contents for e30V

Page 1: ...scription The E30V model is a digital microprocessor electronic ther mometer with NTC input probes equipped with functions for temperature alarms The instrument is available with a keyboard or without...

Page 2: ...eter at this point i possible to program the instrument in the same way previously described The password protection can be disabled by setting tPP oF Normal mode 2 s 5 s Increase value Decrease value...

Page 3: ...er must ensure that the EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35...

Page 4: ...be used Furthermore the input cable of the probe has to be kept sepa rate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground at only one side 4 3...

Page 5: ...nt the A01 must be correctly supplied AC supply Supply adapter 12 VDC Enter PWS 12 V A B C TTL USB to PC USB For additional info please have a look at the A01 instruc tion manual 7 PROGRAMMABLE PARAME...

Page 6: ...andards in force on waste disposal 9 TECHNICAL DATA 9 1 Electrical characteristics Power supply 230 VAC 115 VAC 24 VAC VDC 12 VAC VDC 10 AC frequency 50 60 Hz Power consumption about 2 VA Inputs 1 inp...

Page 7: ...30 VAC C 115 VAC L 24 VAC VDC F 12 VAC VDC b NOT USED d DISPLAY I Red standard C Blue c TERMINALS V Screw terminals standard E Complete removable screw terminals N Removable screw terminals fixed part...

Page 8: ...Ascon Tecnologic e30V OPERATING INSTRUCTIONS PAG 8...

Reviews: